Whether inside or outside of the building, shall be red brass, ductile iron, hard tempered type”K” copper tubing, galvanized steel or other approved corrosion resistant material. All such pipe , other than ductile iron, shall be adequately wrapped or otherwise protected against corrosion.
It is 300 feet.
Each hose connection provided for use by trained personnel (Class 2 and Class 3 systems) shall be equipped with not more than 125 feet of listed , 101/2 inches, lined, collapsible or noncollapsible fire hose attached and ready for use.
Hose connections shall have nominal 2-1/2 inch threads conforming to FDNY standards.
Siamese connections shall be placed between 18 inches and 36 inches above the sidewalk level.
65 psi.
In heights of 300 feet ( 30 story).
? 1. All times in stair inclosure.
2. It shall be between 3’ and 5’ above the floor. ?
They shall be readily accessible for inspection, repair, and use. If the valve is placed so that its operating mechanism is more than 7 feet above a floor or stair landing,a 12 inch wide wrought iron, steel or equivalent ladder securely fastened shall be provided for access to the valve.