The pressure on the supply as well as the return side of the system can very.
When the vacuum pump cycles off, the pressure in the supply and return piping equalizes. If there is a call for heat and a radiator valve opens there is no steam flow, because there is no pressure differential. In order to make sure there is always steam circulation a differential controller must be installed. The differential controller maintains a pressure differential between the supply and return sides of the system.
Device that maintains the pressure difference between the supply and return piping in a sub-atmospheric steam heating system. The controller is factory set to maintain this differential. It starts and stops the vacuum pump thus maintaining the system differential. For example, if the vacuum in the steam supply is at 10”, the pump will maintain 12” of vacuum in return piping.
Near the end of the steam main farthest from the control valve, it may, if necessary be located near the vacuum pump.
Zone valve must be installed in a horizontal main and never in a vertical pipe. There should be at least 10’ of straight pipe beyond the control valve.
A pressure of 2 to 10 psig should be maintained ahead of the control valve at all times while the system is in operation. A compound gage with a pipe siphon should be installed about 10’ from the control valve.
By either a low voltage electric motor, a pneumatic relay, or a combination pneumatic-electric relay according to the temperature reading at the window selector and room thermostat, as corrected by the heat balancer.
It is used to measure the heat supply rate.
It is specially constructed convector with its heating element connected to the supply and return piping. Two resistance coils, one located below the heating element and the other located above, measure the temperature of the air entering and leaving the heat balancer. Any variation in steam supply to the system is thus measured and the extent of the control valve opening is automatically changed to balance the heat supply with the heat demand.
It should be located between 1/4 and 1/2 the distance from the control valve to the end of the longest steam main. It should not be located close to the control valve and not closer than 5’ to an elbow or offset in the main. It should never be installed so close to steam piping that the inlet air temperature would be affected. The heat balancer should be installed in a room with a normal air temperature of not less than 60F or more than 80 F.
The control panel takes continuous readings of the existing heating conditions in the system and of the amount of heat being supplied. If the steam supply is not in accord with heat demand the position of the control valve is changed accordingly. Any change in control valve setting is limited to approximately 3% per minute. This is done so there are no radical changes in the pressure and steam temperature in the system piping.
The outdoor sensor and the system thermostat are both considered external control devices.
They send data back to the control panel. This data along with the information provided by the heat balancer determines the degree of opening of the control valve and the amount of heat supplied to the system heating units.
It must be protected from the direct rays of the sun.
It is a simple temperature sensing device. The thermostat serves as a high and low-limit control when other than normal temperatures exist in the building or zone. In addition to controlling the heat up period, the thermostat is also in command of steam flow during the night and during weekend shutdowns, when the selector switch of the control panel is positioned manually or changed automatically by the time switch assembly.
The design engineer specifies a hydrostatic or steam pressure test. This is followed by a vacuum test.
A vacuum pump lowers system pressure to 20” Hg. The pump is shut off and after two hours, a vacuum of at least 17” Hg must remain in the system. If there is hess the system is not tight and all leaks must be repaired.
They must operate at any pressure from 15 psig to 26” Hg. Many steam traps will operate down to 15” Hg.At vacuum deeper than 15” the traps will snap shut, preventing circulation.