What is the prerequisite for 311 AFFF Operator?
306 Basic Damage Control.
What is required to test out of 311?
Pass written test before oral board; PQS fully completed; check POD for dates.
What is AFFF and its purpose?
Aqueous Film Forming Foam; creates film over flammable liquids to exclude oxygen, prevent vapor formation, and cool surface.
What is AFFF composition?
94% seawater, 6% concentrate.
What types of fires is AFFF used for?
Primarily Class Bravo and Class Alpha fires.
What is H2S?
Hydrogen sulfide, colorless, flammable, poisonous gas with rotten egg smell; toxic, corrosive; found in CHT, firemain, AFFF piping/tanks.
What actions if H2S suspected?
Stop, evacuate, report to Fire Marshal/DCC immediately.
What are environmental rules for AFFF discharge?
Authorized beyond 12 nm. Between 3–12 nm allowed if ship speed ≤10 knots. In port must discharge to tank/barge/truck.
Where are Essex’s AFFF stations?
Station 1: FWD STBD outside Hazmat. Station 2: by Repair 2A. Station 3: I-10 P-way. Station 4: CHAPS P-way. Station 5: Aft hangar bay by Repair 3. Station 6: Mid hangar bay port by 1H.
What are piping colors for AFFF?
Red/Blue = concentrate. Red/Green = mixture. Red = firemain.
What is the AFFF tank capacity and material?
2000 gal, copper-nickel construction.
What pumps are installed?
2 pumps: Alpha (groups/zones), Bravo (hose reels).
What does Master SOPV do?
Starts AFFF pump, opens hycheck and powercheck valves.
What does Service SOPV do?
Routes AFFF to designated group, zone, or hose reel.
What does the power panel indicate?
Shows available power at station.
What do hose reels provide?
50 ft rubber hose with 1?-in vari nozzle.
What is the powercheck valve?
Diaphragm, seawater pressure operated; gateway for mixing AFFF with firemain; prevents backflow.
What is the hycheck valve?
Diaphragm, seawater operated; controls station output of AFFF to spaces.
What is the powertrol valve?
Normally closed diaphragm valve; seawater operated; allows finished foam to flow to designated spaces.
What is the sound-powered phone circuit for AFFF?
X50J, connects station to DC Central; backup = messenger/runner/Hydra radio.
What is required of AFFF operator during ops?
Remain on station, maintain comms with DCC.
What is an in-line AFFF eductor and how does it work?
Used with 95 GPM nozzle; seawater passes through eductor creating suction; draws concentrate from 5-gal container/55-gal drum; mixes at ~6% when inlet pressure = 100 PSIG; ~5 gal/min concentrate consumed.
What document provides valve alignment steps?
Engineering Operational Sequencing System (EOSS).
What must operator verify on station before ops?
Power panel light white, FM gauges 165–170 PSI, TLI >95%, alignment correct.