A PLC is best mounted in a motor control centre. True or False?
False
Communication cables must be kept a minimum of ____mm from power cables and cross the power cables at ________
300mm, right angles
Grounding and shielding is done in a _______ fashion to prevent ________ loops
radial, ground
Does the CEC allow the load side of a DC power supply (system) to be left ungrounded? What is usually done? Why?
Yes. CEC Rule 10-102(1) allows this if it is not more than 50V. It is usually grounded anyway, to prevent the above-ground potential from becoming excessive through static charging, misconnection or wiring fault.
What are five possible CPU power supply sources in order from least to most preferable
What are four reasons to include a master control relay in a PLC program?
Override for: