Which of the heat rejection loops are represented by an HVAC system consisting of air-cooled chillers feeding fan coil units?
In a system served by series fan powered boxes, the airflow into the space during occupied hours is:
Constant Volume
By definition, DX systems can NOT be water cooled (T/F)
False
In a split system which of the refrigeration lines run between outdoors and indoors components and which of the lines is insulated?
What value accounts for the thermal mass of a roof or wall?
CLTD
What would NOT be considered a space load?
Return air heat pickup
A window facing which direction would be expected to have a higher solar radiation load at 8AM?
East
The air handling has a comparative enthalpy economizer. The return air enters the mixing box at 80/62. The outside air is 85/60. Will the economizer engage?
Yes
The AHU system you are designing has a draw-thru fan with 5 degrees of motor heat. Will you need to use a phantom line to determine the off coil?
Yes
In what year did Trane enter the HVAC Controls business?
1978
What are the top 3 deliverables for a BAS system design?
ASHRAE 62.1 defines the rules for use in airside economizers (T/F)
False
What is the name of the economizer mode where it’s OK to economize with the outside temperature below the return air temperature, but above the supply air temperature setpoint?
Integrated Economizer
What remains constant as refrigerant moves through the expansion device?
Enthalpy
Subcooling decrease the refrigeration effect (T/F)
False
The amount of heat in the refrigerant leaving the evaporator is ____ the amount of heat in the refrigerant leaving the condenser
Greater Than
What is the term for the acoustical energy emitted by the sound source? It is not affected by the environment.
Sound Power
In order to perform S-P-R acoustical analysis, equipment sound information should be presented in terms of…
Sound Power
A size 24 Q fan is selected to deliver 11,000 CFM and develop 4” wg of static pressure. After installation, the fan delivers 9,500 CFM and spins at 2405 RPM. Why is the actual airflow lower than the design airflow?
The system static pressure is higher than 4” wg and the fan rode the fan performance curve to a different operating point
According to the affinity laws, a 10% increase in fan CFM results in a ____ increase in fan BHP
33%
Which method of sizing ductwork tends to be self-balancing and remains relatively well balanced even under conditions of varying flow rate?
Static Regain Method
The Bernoulli Equation is a representation of what?
The conservation of energy
What Tracer BAS product is at the enterprise level?
Tracer Ensemble
What Tracer BAS product is at the unit level?
Symbio