What types of loads on the structure – as defined in ASCE 7 – should be considered while designing a data center?
What are the minimum floor loading requirements for a data center floor?
7.2 kPa (150 lbf/ft^2) with 1.2 kPa (25 lbf/ft^2) hanging dead load (weight that can be supported from the underside of the floor or roof.
What should be the minimum superimposed live load for the battery room floors?
1221 to 2441 kg/m^2 (250 to 500 lbf/ft^2)
What should the minimum suspended dead load for the roof areas over battery rooms?
146 kg/m^2 (30 lbf/ft^2)
What measure is commonly used for wind-loading calculations in the design of data centers?
The enhanced Fujita Scale level of EF3.
What mitigation strategies should be in place to ensure that a data center can function following a major seismic event?
What mitigation strategies should be in place to protect a data center from the ice impact from the ice shedding from the adjacent communication or broadcast towers?
What is the most common type of terrorist attack?
A blast or explosion from some manner of vehicle-borne improvised explosive device (VBIED)
Regarding terrorism, what does the acronym “VBIED” mean?
vehicle-borne improvised explosive device (VBIED)
What are some anti-terrorism measures that should be considered when designing a data center?
What is the most common use of the Enhanced Fujita Scale?
To measure wind-loading calculations
Using a base isolation for access floors and dampers to provide base isolation and building energy dissipation are strategies to ensure a data center can function following what event?
A major seismic event
Adding heating elements on the tower to preclude the formation of ice is one measure against what possibility?
the ice impact from the ice shedding from the adjacent communication or broadcast towers could have on the data center.