Exposed soil or waste piping shall not be installed _______ any working ,storage or eating surfaces in a food service establishment.

A

Above. 701.9

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

2 1/2 inch or less horizontal drainage pipe shall slope a minimum of ______ inch per foot.

A

1/4 in. Table 704.1

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

The size of the drainage piping shall not be ________ in size in the direction of flow.

A

Reduced

A 4” x 3” water closet connection is okay. 704.2

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

Pipe-joint compound or tape shall be applied on the _______ threads only.

A

Male 705.12.1

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

All horizontal drains shall be provided with cleanouts located not more than_______ feet apart.

A

100ft
And at each change of direction greater than 45
708.3.1

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Cleanouts shall be the same nominal size as the pipe they serve up to _______ inches.

A

4”

708.7

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

Cleanouts on 6” and smaller pipes shall be provided with a clearance of not less than ____ inches in front of the cleanout.

A

18”

708.8

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

The minimum trap size for unlisted fixtures shall be the size of the drainage outlet but not less than______ inches.

A

1 1/4 “

709.2

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

Sump pits shall be not less than ___ inches in diameter and 24 inches deep.

A

18 inch

712.3.2

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

A floor drain installed a public restroom with a 3” trap has a DFU of what?

A

5DFU’s

Table 709.1

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

The minimum size of a building drain or sewer that serve a water closet?

A

3 inch

Table 710.1(1) footnote

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

Where the finished floor level on which plumbing fixtures are installed is below the elevation of the manhole cover of the next upstream manhole,the fixtures shall be protected by a ______.

A

Backwater valve

715.1

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

When make a solvent cement joint on PVC pipe the primer shall be of what color?

A

Purple

705.8.2 ; 705.14.2

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

What valves shall be installed in the discharge of a sewage ejector pump ?

A

Check valve ; a full open valve

712.2

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

A sewage ejector discharge line that ties into a horizontal drainage line shall do ____ pipe diameters from any other connection and shall do so through a ___ fitting into the top of the drainage piping.

A

10 pipe diameters ; a wye fitting

712.3.5

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

The minimum size trap serving a shower shall be not less than ____.

A

1 1/2”

Table 709.1

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
17
Q

The maximum waste water temperature that discharges into the drainage system?

A

140 degrees F

701.7

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
18
Q

The DFU value for the discharge from a condensate pump is computed how?

A

1gpm equals 2DFU’s

709.3

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
19
Q

Joints between borosilicate glass pipe and others of piping materials shall have what type of seal?

A

TFE ( Teflon)

705.19.6

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
20
Q

When the DFU load of a fixture is not found in table 709.1 , how is the DFU load calculated?

A

By trap size

709.2 ; Table 709.2

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
21
Q

The minimum slope that a 3 to 6 inch horizontal drainpipe may be installed is_____.

A

1/8 in/ft

Table 704.1

22
Q

Horizontal branches that connect downstream of the base of a stack shall connect not less than _____ downstream from the stack.

A

10 times the diameter of the stack

704.3

23
Q

Cast iron lead-chaulked joint for hub & spigot soil pipe shall be filled with molten lead not less than __ inch deep and not to extend more than ____ below the rim of the hub.

A
1 inch(25mm); 1/8 inch (3.2mm)
705.5.1
24
Q

Cleanouts shall be installed at each change of direction of the building drain or horizontal waste or soil lines_______ and where more than one change of direction occur in a run of piping,only one cleanout shall be required for each ____ feet of developed length of the drainage line.

A

greater than 45 degrees; 40 feet

708.3.3

25
All horizontal drains within a building shall be provided with cleanouts located not more than ______ feet apart.
100 | 708.3.1
26
Sanitary tee pattern fittings shall be used in a drainage system when the flow of waste is________.
Horizontal to vertical | table 706.3
27
Where a floor drain receives only clear-water from coolers and freezers, the floor drain is assigned value of _____ DFU's.
1/2 a DFU | 709.4.1
28
A 4" diameter building drain installed with a slope of 1/4 inch per foot has a capacity of not more than how many DFU'S?
216 DFUs | Table 710.1(1)
29
For a 2- inch horizontal branch drain less than 30 feet long,what is allowed to serve as a cleanout for the drain?
1 1/2 " slip joint trap | 708.7 Exception 1
30
The DFU load from a clinical sink with a 3" trap is ___.
5DFUs | 709.2 & Table 709.2
31
A sump pump with a discharge of 10 GPM that discharges through a 2-inch indirect waste receptor has a DFU of ____.
20 DFUs | 709.3
32
A private bathroom with a 1.6 GPF toilet , lavatory ,bathtub,bidet and floor drain has a total DFU of____.
5 DFUs | Table 709.1 & 202
33
The minimum size building drain serving a toilet is ___ inches.
3" | Table 710.1(1) Footnote A
34
A vertical distance of ___ feet or more between the connection of horizontal branches to the drainage stack is a branch interval.
8 FEET | 202
35
In a building with a basement subdrain sump, what is prohibited from discharging to the sump?
drainage above the gravity sewer | 712.1
36
A ____ is not required for a sewage sump and ejector.
Pump alarm | 712.2 & 712.3.2
37
The ejector pump on float shall be set to prevent the effluent in the sump from rising to within ___ inches of the invent of the gravity drain inlet.
2" | 712.3.4
38
Sewage grinder pumps that receive the discharge of toilets shall have a minimum discharge of ___ inches.
1 1/4 " | 712.4.2 exception 1
39
What is the minimum required capacity of a 2" sewage ejector?
21 GPM | Table 712.4.2
40
A ______ shall be vented to the atmosphere with a minimum 2" vent.
bedpan washer | 713.9
41
Which health care fixture is required to discharge through an air gap into an indirect waste receptor?
Bedpan steamer | 713.3
42
A fully open backwater valve shall have a flow capacity of ____ percent of the pipe served.
100% | 715.4
43
The air flow velocity of a central vacuum system shall be less than ____ FPM.
5000 Feet per minute | 713.7.2
44
A cleanout shall be provided at the base of each ____ stack.
Waste | 708.3.4
45
What is the minimum clearance required in front of a cleanout for a 2" drainage pipe?
18 inches | 708.8
46
The minimum size branch piping for one vacuum outlet is _____nominal pipe size.
1/2" | 713.7.1
47
The minimum size main piping for a central vacuum system is _____ nominal pipe size.
1" | 713.7.1
48
The local vent from a bedpan washer or sterilizer is prohibited from connecting to the __________.
Normal sanitary plumbing system | 713.8
49
Horizontal branch connections above or below vertical stack offsets within ___ feet and located more than four branch intervals below the top of the stack, the offset shall be vented in accordance with section 906.
2 feet | 711.1
50
Backwater valves shall be installed so that _____ is provided to the working parts for service and repair.
Access | 715.5