DG Emergency Start Signals
Safety Injection (Starts Unit Specific / Other DGs start from CES)
6.9kv Board Undervoltage
Loss of 125v DC
DG Engine Protection (Normal Start)
Low Lube Oil Pressure: 20 pasig
High Jacket Water Temperature: 205 F
Over speed: 1035 rpm
DG Generator Protection (Normal Start)
Differential (87)
Phase Balance (46)
Reverse Power (32)
Loss of Field Relay (40)
DG Common Emergency Start Protection
Engine Overspeed: 1035 rpm
Differential
DG ERCW Supplies
1A and 2A DGs Normal: 1A Header
1A and 2A DGs Alternate: 2B Header
1B and 2B DGs Normal: 1B Header
1B and 2B DGs Alternate: 2A Header