What is the name of the O2 controller for the super heater?
AIC 6040B
What is the controller name for the Aux?
AIC 6062B
What control state is AIC 6062B in normally?
Why?
CAS
It generates its set point based off Aux steam out put. The lower the out put the higher the excess O2 percent will be. This gives a buffer for quick changes in steam demand.
What does the
Air controller set point divided
How does the AIC-6062B work.
The PLC multiplies the actual air flow by 1.03 then divides this number by the excess air controller OP.
What does a OP of under 1 mean?
To much excess air.
What does a OP of over 1 mean?
The controller is asking for more excess O2.