All Steps 1-11
for cracked glass, loose wiring, and proper voltage rating
Gloves, face protection, hard hat, vest, boots, clothing
for damaged clips, loose screws, foreign matter, broken parts
Verify customer main is open
Test the tester on a known live source
Continuity test
- phase to ground should be no light
-neutral to ground should light
-phase to ground should be no light
Test 1 - source voltage - line side to neutral should be 120V, then line side to line side should read 240V
Test 2 - backfeed - load side terminals to ground source, should read 0 volts
Test 3 - load side - phase to ground fault, test from line to load side, should read 0 volts
** verify continuity of jumper if applicable
Test 4 - load side - phase to phase fault, install jumper from one load side to neutral, then test from line to load side, should read 0 volts. Remove temporary jumper.
…load side for proper voltage if possible
… Meter ring and meter seal
… Customer’s main, if applicable
***Before any of these steps ensure customer’s main panel is connected properly and safe to liven up if possible to enter