What marking must each service box carry at the time of installation?
The maximum rating of the overcurrent device
Source: 2-100(2), CEC, 2021 P 74
Can acid be used for soldering in the electrical installation?
No, shall be non-corrosive to copper
Source: 2-118, CEC, 2021, P75
What must be done if a firewall is pierced by an electrical cable or raceway?
Shall be properly closed or sealed
Source: 2-128(2), CEC, 2021, P76
Can a 3-way or 4-way switch be considered as a disconnecting means?
No
Source: 2-304(2), CEC, 2021 P 77
Cct breaker, fuses and switches shall be conspicuously marked to clearly indicate, what?
A - which installation they protect
B - Maximum rating of overcurrent device permitted
Source: 2-100(3), CEC, 2021 P74
Can wood be used to anchor electrical equipment into masonry or concrete?
No
Source: 2-114, CEC, 2021, P75
What is the maximum voltage to ground permitted by the code for branch circuits in residential occupancies where no trained personnel are available?
150volt to ground
Source: 2-110, CEC, 2021 P75
What is the minimum working space required by the code for a switch board that contains renewable parts at the back?
1m
Source: 2-308(1), CEC, 2021 P77
What is the maximum branch circuit voltage-to-ground for a single-family dwelling?
150v
Source: 2-110, CEC, 2021 P 75
Can NMSC (Non-metallic sheathed cable) be used for wiring purposes in the attic of a single-family residence where zonolite fill ( a loose or free flowing insulation) is used as thermal insulation?
Yes
Source: 2-126(1) b, CEC, 2021 P75
An apartment building has a calculated load of 250 KVA on the service conductors. It employs a full-time maintenance electrician to look after any installation. What is the maximum voltage-to-ground for the fixed heaters installed in each apartment allowable under the code?
150 Volts - does not exceed 250 KVA to allow 347 / 600V
Source: 2-110, CEC, 2021 P 75
A high rise office tower has a calculated load of 500 KVA on the service conductors has central air conditioning and water heating facilities. Space heating is accomplished by electric heating. The building employs a FT maintenance electrician. Will the installation of florescent light fixtures have to comply with the maximum of 150 volts-to-ground for branch cct rule as specified in the code?
No, this is not a dwelling unit. Office, not sleeping.
Source: Section 0, Definition, CEC, 2021 p 61
Can a mineral insulated cable such as pyrotenax which has an outer skin made of copper be used in an installation that employs aluminium foil as a heat reflector in the ceiling? The purotenax cable is used as an electric heating cable in the ceiling.
No.
How many entrances be provided to give access to the working space about electrical equipment?
At least 1
Source: 2-310, CEC, 2021 p 78
Where the code makes reference to AWG wire size with no specific designation attached, what do they mean?
Unless otherwise specified, Copper AWG size
Source: 2-120, CEC, 2021 P75