Type CL3P is NOT permitted to be used _______.
in direct underground burial applications
An antenna discharge unit is not required for lead-in conductors where _______.
they are enclosed in a continuous metallic shield that is grounded
The largest size conductor permitted within a concrete cellular floor raceway is _______.
1/0 AWG
Omitting exceptions, the work space in front of a panelboard shall be clear and extend from the floor to a height of at least _______.
6.5 feet
Omitting exceptions, which of the following materials is NOT permitted to be run vertically within ducts specifically fabricated to transport environmental air?
FMC
NM-B***
NEEDS VERIFICATION
All Type FCC cable connections shall use connectors identified for _______.
sealing against dampness and liquid spillage
Excluding exceptions, network-powered broadband communications cables attached to a structure and located within _______ of finished grade shall be protected by enclosures.
8 ft
If new products, not yet available at the time when the Code was adopted, are made available, who may permit the use of these products?
Authority having jurisdiction.
The first isolated circuit conductor that is provided for in a health care facility is the color _______.
orange
The minimum size copper equipment grounding conductor that is used for a 100 ampere rated disconnect is a/an _______.
8 AWG
Which of these is not required to be shown on a control drawing?
Simple apparatus
An alarm panel board with a voltage of 50 volts to ground is installed. The minimum depth of the working space is ________.
3 ft
Electrical systems that are grounded shall be connected to earth in a manner that will provide for all of the following EXCEPT?
Unlimit the voltage imposed by intentional contact with higher-voltage lines.
Where nonmetallic-sheathed cables pass through a factory drilled hole in metal members, the cable shall be protected by _______.
listed bushings
Where installing Type IMC in Class 1 locations, factory threaded NPT entries shall be up of at least _______ threads fully engaged.
five
four and one-half
***NEEDS VERIVICATION
In Class I, Division 1 locations, a conduit seal shall be installed within _______ from an enclosure.
18 in.
Where nipples having a maximum length not to exceed 24 in. are installed between boxes, the nipples shall be permitted to be filled to _______ of their total cross-sectional area.
60%
A transformer supplies a Class 2 circuit. It’s input leads are 16 AWG. What is the maximum length of the input leads?
12 in
Nonmetallic auxiliary gutters shall be supported at intervals not to exceed _______ and at each end or joint.
3 ft
The minimum depth that a 6 inch rigid conduit may be placed under the tarmac of an airport is _______.
18 in.
Four lead-in conductors are used for an outdoor antenna. How many antenna discharge units are required?
4
Underground service conductors are buried at least 18 in. below grade. These conductors shall have their location identified by a warning ribbon that is placed in the trench at least _______ above the underground installation.
12 in.
Fuel dispensing systems shall be provided with at least one clearly identified emergency shutoff device. This device is to be installed in approved locations not less than _______ from the fuel dispensing devices that they serve.
20 ft or more than 100 ft
Which of the following IS considered to be safety-control equipment that is used in conjunction with electrically controlled household heating and air conditioning?
Room thermostat.
ALL LISTED are NOT considered safety-control equipment
***NEEDS VERIFICATION