What are the NESW pump trips?
What NESW pump autostarts do you get when the switch is in Auto?
Do the NESW pump discharge valves auto open on a manual start signal?
If the NESW pump switch is in auto, how must the discharge valve be arranged?
How soon after a Load Conservation can a NESW pump be restarted and how is it done?
What are the NESW pump suction sources?
Both Units: -CW Intake Tunnel (Normal) -Discharge Tunnel (Alt)
What are the NESW pump power supplies?
Which NESW header has the glycol loads on it?
When does WMO-906 (NESW Misc header supply valve) auto close?
At what DP do the NESW Duplex strainers auto backwash at?
When do both units NESW Duplex Strainer backwash alarms come in?
95” H20 - Unit 197” H20 - Unit 2
What does T.S. 3.6.3 B (Cnt Isolation Valves) state?
If 2 CIV’s are inopWITHIN 1 hr:- Isolate penetration
Which valves isolate on a load shed in the NESW system and why?
L.O. cooler WRV’s close:- maximizes flow the PAC, CAC, CLVs (If in Open Loop) - lowers load on EDG by lowering load on NESW
Which unit’s NESW supplies the Seal Oil Coolers?
Which unit’s NESW supplies the TSC Air conditioning?
When does the NESW header supply the Containment vent units, blowdown heat exchanger and blowdown sample heat exchanger?
What loads are on the NESW Misc Header?
What is cooled by the NESW Norm Header?
What NESW pump autostarts do you get when the switch is in neutral?
What is the most important load on the NESW Misc Header?
What has to be done in order to reset the Lube Oil Cooler WRVs after a load shed?
When do the LO Cooler WMOs get a close signal and when can they be operated after?
Load Conservation, they can be operated 75 sec after a load con
Which Containment Isolation Valves don’t isolate on a Load Conservation?
Which Containment Isolation Valves isolate on a Load Conservation?