Purpose of P.E.C. 2009:
Mandatory Rules, Permissive Rules, & Explanatory Material:
Coverage or Scope of PEC 2009
Covered-The installation of electrical conductors, equipment, and raceways; signaling and communications conductors, equipment, and raceways; and optical fiber cables and raceways installed.
Coverage or Scope of PEC 2009
Not Covered - The following installations are not covered:
PERMITS AND INSPECTION CERTIFICATES
Places to Obtain Permits:
* Marina(Maritime Industry Authority) - watercrafts
PERMITS AND INSPECTION CERTIFICATES
Requirements for Electrical Permit:
a) Information
1. Applicant
2. PEE who signed and sealed the electrical plans and specifications
3. Licensed Electrical Practitioner who is in charge of electrical works
4. Building Owner
5. Lot Owner
6. Building Official
b) 5 SETS of complete electrical plans and specifications signed and sealed by PEE
The delay for releasing an electrical permit shall not be longer than five (5) working days after which time application together with the accompanying plans
PERMITS AND INSPECTION CERTIFICATES
Reconnection of Disconnected Service
ELECTRICAL PLANS AND SPECIFICATIONS
Drawing Sheet Sizes
760 mm x 1,000 mm
600 mm x 900 mm
500 mm x 760 mm
ELECTRICAL PLANS AND SPECIFICATIONS
Plan Requirements:
a) Location and Site Plans
b) Legend or Symbols
c) General Notes and/or Specifications
d) Electrical Layout
e) Schedule of Loads
f) Design Analysis
g) One Line Diagram
ELECTRICAL PLANS AND SPECIFICATIONS
Title Block or Nameplate of Plans and Drawing
ELECTRICAL PLANS AND SPECIFICATIONS
Other Details for Electrical Plans
ELECTRICAL PLANS AND SPECIFICATIONS
Substation Plans and Specifications
-Outdoor Substation
SHALL show same items as indoor substation except that in lieu of walls and roof, details of fence and supporting steel structure.
REQUIREMENTS FOR ELECTRICAL INSTALLATIONS
The Criteria for Examination of Electrical Inspection:
REQUIREMENTS FOR ELECTRICAL INSTALLATIONS
Entrance to Working Space
a) Large equipment - equipments rated 1200 amperes or more shall have at least one entrance.
600 mm wide
2000 mm high
b) Headroom - The minimum headroom of working spaces about service equipment, switchboards, panelboards, or motor control centers shall be 2000 mm.
REQUIREMENTS FOR ELECTRICAL INSTALLATIONS
Warning Sign for Voltages Exceeding 600 Volts
―DANGER - HIGH VOLTAGE - KEEP OUT‖
REQUIREMENTS FOR ELECTRICAL INSTALLATIONS
Measurements for Access to Manholes
a) Rectangular access openings (650 mm x 550mm)
b) Round access openings (650 mm diameter)
.
.