the full load current, or full load amp rating of any electric motor is the ______________________ it can safely draw from the line
max amt of current
where to find FLC rating on a motor
name plate
what table in the CEC is used to determine motors FLC
table 45
how to find minimum code conductor ampacity and from what code rule
What table to find trade size conductors
T 1,2,3,4……
what code rule to find temperature limitations for conductors
CEC 4-006
Can trade size conductors be smaller then CEC calculated conductor ampacity
NO
Every electric motor and its branch cct require a ______________ means and some sort of __________ protection
-diconnecting
-overcurrent
What are type P fuses
non time delay
what are type D fuses
time delay
what are the 3 types of overcurrent devices
-type P fuses (non time delay)
type D (time delay)
-cct breakers
Why do motors create a surge when the electric motor starts
-large inrush current needed to start the electric motor
What code rule and table is used to size overcurrent devices
-CEC 28-200
-Table 29
What are standard trade sizes for saftey switches
30,60,100,200,400,600A
In non-fused switches the ampere rating of the load determines the _____________ size
disconnect switches
In fused diconnects, the ampere rating of the chosen fuse determines the ___________________ size
disconnect switch
What are bonding conductors used for
bond to ground the non-current carrying metal parts of the electric motors branch cct
What section of the CEC indicates about bonding and what table
section 10
- 10-616 1)
-Table 16
does the bonding conductor need to be larger then the supply conductor
no
What CEC section is used for overloads
26-306
A motor drawing more current than its FLC is ______________
overloaded
What happens if a motor is overloaded
-motor overheats
-burn out motor windings
What is the purpose of the overload device
-shut down the motor before its windings are destroyed
overload devices operate on a _______________ baisis
time-lags