BTU
British Thermal Unit - amount of heat that it takes to move 1lb of water up 1 degree (F)
When wet bulb and dry bulb temperatures are the same, what does this mean?
Relative humidity is 100% because there is no moisture being evaporated from wet bulb to cool it off.
Altitude
Sun’s angular height in the sky taken from the horizon.
Azimuth
Sun’s angular position in the sky east/west of south.
Conductivity (k)
Heat transfer through homogenous material (per inch)
Resistivity
Heat transfer inefficiency through homogenous material (per inch)
Conductance
Heat transfer through homogenous or heterogenous material of a given thickness
Resistance
Heat transfer inefficiency through homogenous or heterogenous material of a given thickness
Conduction equation
Q = U x A x ΔT
Convection Equation
Q = 1.08 x CFM x ΔT
Coolant that is evaporating is ______ (warm/cool)
Cool
Coolant that is condensing is ______ (warm/cool)
Warm
Boiling point of water
212 degrees (F)
Ideal duct aspect ratio
3:1
What is free cooling?
Economizer cooling. Using the free coolth from the outside to chill your coolant. A switch is activated to bypass compression refrigeration during cooler months (but not when it is too cold).
Ground Source Heat Pump
Water loop sent down through the ground to heat / cool in winter / summer and sent up to the compression coil to heat / cool the coils in contact with the coolant.
Grill
Intake
Register
Supply air “vent”
Diffuser
Air vent that dumps air into a room directionally to diffuse the air
Single Zone System
1 AHU per thermostat / zone. Requires lots of space on the roof if lots of zones are needed. Lots of space is lost to ductwork.
Variable Air Volume (VAV)
Multiple zones achieved with a single AHU. Dampers inside branch takeoffs that control the flow of conditioned air. Very efficient on space but not as much temperature control as systems that heat & cool simultaneously
Variable Air Volume (VAV) with Terminal Reheat
Dampers inside branch takeoffs to control flow of conditioned air. Added option to reheat the air if the room needs to be warmer. Inefficient because you are cooling air just to reheat it again.
Energy Recovery Ventilator (ERV)
A unit that mixes fresh air intake with already-conditioned exhaust air to only have to heat/cool half of the new air. Very energy efficient but requires a large unit.
Dual Duct System
Each zone has access to fresh warm and cool air. Air is brought in and cooled / heated separately, then combined in a mixing box to achieve desired temperature