Hi level in PWST occurs at ____ and will automatically _____.
95%
Close 0PW008, inlet to tanks
-and-
Close 0WX063, return from SD and wx monitor tanks
Low discharge pressure alarm at discharge of pumps occurs at ____.
Normal pressure is ____.
95#
160#
If the selected PWST level goes below ____, _____ will auto open.
<90%
0PW008
For auto start of 0A or 0B makeup pump, ____ must be in remote, MCB CS ______ and RMCS for associated unit demands flow.
local/remote
MCB CS not in PTL
0PW008 is operated from _____.
rad waste panel
PWST heaters trip off at _____ tank level.
11%
Recycle transfer pumps are controlled by ______ level.
Vacuum catch tank
How is the oxygen minimized in the PWST?
N2 blanket