In order of frequency, what are the 3 types of major faults in an electrical system
Explain an inverse time curve:
As the magnitude of actuated quantity is increased, the amount of time to respond reduces.
What are the 2 main ways that a relay operates?
Explain how a Distance Relay (21) works:
It measures impedance on the line.
True or False?
Zones of protection can be overlapped to avoid leaving unprotected areas.
True.
what is an RTD and where are they located?
Resistance Temperature Detector.
Located in critical temperature areas.
Explain how an Armortisseur Winding temp relay (26) works.
Through the use of a CT, It measures for excessive field current, which suggests overheating.
True or False?
Loss of Field relay (40) prevents system instability?
True
RTDs, CTs, and PTs are examples of what part of the protective relay system?
Sensors
What are the 5 groups of relays and what do each do?
True or False?
Protective relays may trip devices in more than one circuit.
True
What is a 59N and how does it function?
59N = Neutral Overvoltage Relay
If the neutral of a 3-phase AC system develops a current flowing through it (normally zero), then a “distribution xfmr” has a current induced unto a secondary winding. This current is then passed through a resistor. If the voltage is high enough to overcome the resistance of the resistor (pre-determined level) then the voltage passes through a 59N relay.
A Differential relay (87) protects against what?
INTERNAL ground fault that causes differentials in voltage or current
What are the 2 groups of protective relays?
Explain the difference between an “A” contact and a “B” contact
“A” = normally open, and closes when energized
(reflects the position of the main breaker)
“B” = normally closed, and opens when energized
(reflects opposite of the position of main breaker)
Explain a Sudden Pressure relay (63). What causes it?
When internal faults occur inside a xfmr, the oil temp rises suddenly. This rise in temp creates gases. These gases trip the sudden pressure relay (63)
note: a gradual rise in temp will not trip this relay. ie - if the oil temp rises as atmospheric temp rises with seasons
True or False
Distance relays (21) measure impedance at the relay location?
True
Explain a 51V. What makes it special compared to other 51 relay? Why?
A 51V reacts to both changes in current AND voltage.
The reason being…. during motor START-UP a large inrush of current is expected. So to keep from tripping the 51V also looks for a large change in voltage. Which is not supposed to occur on start-up.
What are 4 characteristics used to identify a fault?
According to 600.12, what protective devices can only be reset by the cheif operator or designee after trip? Which relay is additional to SOO #3?
Differential relays (87)
Ground fault relays (64)
Sudden pressure device (63)
SOO#3 = 59N Overvoltage
What does SEO stand for and where can it be found?
Series of Events; It can be found in:
What protects generators and the grid from line instability caused by loss of excitation?
Field Relay (40) - Loss of Excitation.
What type of device is used to measure amortisuer winding temperature?
CT
What is DWR’s protective relaying maintenance policy?
MM_29