Rubber gloving ____ to _____ volts phase to phase
7,500 to 21,000
Primary zone- the area is within ___ of reaching or falling distance from energized conductors or equipment
28”
Class 00
Beige
Class 0
Red
Class1
White
Class 2
Yellow
Class 3
Green
Class 4
Orange
Class 00 Beige is tested at ____ and max rated use _____
(2,500) (500V)
Class 0 Red is tested at ____ and max rated use _____
(5,000) (1,000V)
Class 1 White is tested at ____ and max rated use _____
(10,000) (7,500V)
Class 2 Yellow is tested at ____ and max rated use _____
(20,000) (17,000)
Class 3 Green is tested at ____ and max rated use _____
(30,000) (26,500)
Class 4 Orange is tested at ____ and max rated use _____
(40,000) (36,000)