Untitled Deck Flashcards

(18 cards)

1
Q

What does AVB stand for?

A

Atmospheric Vacuum Breaker

AVB is used to prevent backsiphonage.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What does PVB stand for?

A

Pressure Vacuum Breaker

PVB is designed to stop backsiphonage.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What does DCA stand for?

A

Double Check Assembly

DCA is used to prevent backpressure.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What does RP stand for?

A

Reduced Pressure Principle Device

RP is used to handle both backsiphonage and backpressure.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

Which devices can stop backsiphonage?

A
  • PVB
  • DCA
  • RP
  • AVB

These devices are effective in preventing backsiphonage.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Which devices can stop backpressure?

A
  • DCA
  • RP

These devices are specifically designed to handle backpressure.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

Which devices can handle constant pressure?

A
  • RP
  • DCA
  • PVB

These devices are suitable for applications with constant pressure.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

The approved backflow devices for non-health hazards include:

A
  • AVB
  • PVB
  • DCA
  • RP

All these devices are approved for non-health hazard applications.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

Which device is approved when there is chemical applied by aspiration, injection, or emission?

A

RP

RP is the only approved device in such scenarios.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

If there is an on-site sewage facility, which backflow device is approved?

A

RP

RP is required when an on-site sewage facility is present.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

If major maintenance has to be performed, which backflow device must be properly installed prior to the repair work?

A

An approved backflow device

Proper installation is crucial before maintenance.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

If including a master valve, where must it be installed?

A

Downstream from the PVB, DCA, or RP

This ensures proper operation of the system.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

Which devices have to be tested upon installation and annually?

A

Devices used in applications designated as health hazards

Regular testing is essential for health hazard applications.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

Which backflow devices have to be tested upon installation?

A

All backflow devices

Testing is mandatory for all backflow devices upon installation.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

If a DCA is installed below ground, what device is required?

A

A Y-Strainer installed on inlet side of the DCA

This is necessary to prevent debris from entering the system.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

If there is an additional water source supplying water to a system being supplied by a potable water supply, what device has to be used?

A

A backflow prevention device

This is crucial to protect the potable water supply.