what is the minimum size for blowdown piping?
3/4’’
Can both LWCO and Aux LWCO be installed with a common pipe?
NO. They have to be piped separately.
Can both LWCO controls be installed on the same water level.
No, One has to lower than the other.
What is the minimum height for the LWCO cut installation?
They have to installed above the highest tubes.
What is the maximum pressure rating for the float type LWCO controls?
150 PSIG
Can both LWCO controls share the stream line piping?
yes
Which plug are recommended for steam piping?
Bull plug
Can shut-off be installed in the piping of LWCO
NEVER.
Which is of automatic and manual reset type : of LWCO and Aux LWCO
LWCO= Automatic reset type
Aux LWC= Manual reset type.
In which circuit the LWCO controls are wired?
The safety circuit.
What type of fittings are to be used for boiler blowdown piping?
cross - for inspection
To protect against a low water condition how many fuel cutoff devices are required on an automatically fired steam boiler?
2
Beside shutting off the burner, what is another function of a low water cut-off device on a steam boiler?
Energize feed pump
What is done to change the operating level of an external float style LWCO device
Change the installation piping
What is the purpose of a steam trap?
It prevents steam from entering the condensate return piping
At what point does the thermostatic steam trap open?
When the condensate temperature drops below saturated steam temperature
What does the thermodynamic steam trap operate on the basis of?
Bernoulli’s principle
The thermodynamic steam trap will work on lower pressure systems.
TRUE / FALSE
FALSE