What is the Max temperature for 316L stainless steel
Max temp 550* F
annex c c.2.5 horizontal length
look book
Type 316L stainless steel vent is common for what purpose / type of appliance
Condensing. As it is resistant to corrosion
What is the Purpose of the vent.
To keep the heat inside and protect the structure outside.
Single wall chimney liners are intended for masonry chimney to vent which category of appliances
Cat 2 , 3 and 4 Gas and oil fired condensing appliances
Double wall insulation vent will require insulation to be placed over or under the bad clamp before the installation of the trim piece?
Over
Low temp sealant rating - ?
High temp sealant rating ?
What is ES
LTS 600F
HTS 2000F
ES exterior sealant - outer sealant weather proof
What is the horizontal grade per foot for vent ?
1/4” / Ft
What is the draft status of an atmospheric appliance referred to as
Gravity
What can be the results of an improperly selected, sized and/or installed venting system?
Efficiency loss, Appliance damage, Increased appliance maintenance, damage to breeching & stack, Production downtime, Increased operating costs.
What is the draft source for a natural draft appliance? Explain how this draft source moves the products of combustion through the appliance and the venting.
Gravity is the source. It moves the products of combustion through the appliance and venting because the hot flue gases are lighter and naturally rise (buoyancy).
Define forced draft:
A mechanical draft produced by a device upstream from the combustion zone of an appliance
Define induced draft:
A mechanical draft produced by a device downstream from the combustion zone of an appliance
Describe the three general variations of Burner inlet blowers and the different pressures associated with each.
a. Blowers which operate with enough pressure to overcome the burner alone. The combustion chamber, appliance outlet and venting will all be under negative pressure
b. Blowers which operate with enough pressure to overcome the burner and combustion chamber. The combustion chamber will be under positive pressure, appliance outlet will be neutral or negative and the appliance venting will be under negative pressure
c. Blower which operates with enough pressure to overcome the burner, combustion chamber and part or all of the venting. All parts of the system past the burner are under positive pressure
What is the pressure upstream of the blower when it is located on the outlet of the appliance?
Negative
What is the pressure downstream of the inducer blower located on the outlet of the appliance?
It will be positive immediately downstream but could be either negative, neutral or positive on the downstream side depending on the blower’s power and the venting system
In a venting or chimney system with mechanical draft what two types of draft can be present and what type of pressure is associated with each?
Forced draft – static pressure in the venting is positive
Induced draft – static pressure is the venting is negative
When a venting system was originally installed as a gravity system where is the best location for the blower to be located? Why?
A draft inducer located at the vent or chimney outlet will maintain a negative pressure in the venting. Which would be the pressure the system was originally designed for
What must be done when a power venter is used in place of a natural draft venting system.
Gas flow to the main burner must be prevented in the event of power venter failure
When must design registration take place when you are designing or modifying complex, technical, and regulated equipment in BC?
Before the construction and installation of the equipment
When are parallel blade damper used?
When are opposed blade dampers used?
PARALLEL For open/closed operation
OPP For modulating operation
What must be done when an automatic flue damper is installed on an appliance with a continuous pilot?
Must have a fixed minimum opening of 20% of the flue area and be interlocked with the burner control system so the that damper is proved fully open before ignition of main burner and The fuel supply to the appliance will be shut off in the event of failure except where the damper will fail fully open.
What is used on flue venting guy wires to allow for vent expansion and contraction without stretching the guy wires?
spring loaded turnbuckle
What Category appliance has nonpositive pressure and a temperature above 140°F (60°C)?
What Category appliance has positive pressure and a temperature below 140°F (60°C)?
What Category appliance has positive pressure and a temperature above 140°F (60°C)?
What Category appliance has nonpositive pressure and a temperature below 140°F (60°C)?
Category I
Category IV
Category III
Category II