How is level maintained in the PZR?
What are the max and min setpoints when in REMOTE AUTO?
What are the associated Tave values for the max and min Lpzr programs
What determines the PLCS setpoints when in Local AUTO?
The operator using the thumbwheel.
What is the AUTO letdown flow limited to by PLCS?
30-135 GPM
State the Lpzr deviation setpoints and what happens at each value.
State the alarms associated with Lpzr and any other associated actions.
How would you determine what the setpoint should be if given a Rx power between 15-100%?
What happens to Lpzr setpoint on a RCS temp instrument that:
Fails HIGH
Fails LOW
Do temp instrument failures affect Lpzr setpoint in Local/Auto?
High: Lpzr setpoint goes to 53% and PLCS responds.
Low: Lpzr setpoint goes to 33% and PLCS responds.
NO
Actual Lpzr = 33%
Lpzr setpoint is shifted due to failure to 53%.
What happens in PLCS?
Remember:
Actual - Setpoint to get deviation. Do the “does this make sense?” check.
ie. Does it make sense that LD would go to maximum if actual Lpzr is already at the low end of the band? NO.
1. LD flow to minimum
2. STBY CHP DOES NOT START!!!! 33 - 53 = - 20%
3. PZR TRBL
Actual Lpzr = 53%
Lpzr setpoint is shifted due to failure to = 33%
How does PLCS respond?
Remember:
Actual - Setpoint = deviation. Do the “does this make sense?” check.
ie. Does it make sense that LD would go to maximum if actual Lpzr is already at the low end of the band? NO.
Deviation = 20%
LD will be lost due to HI HI Regen Temp.
What will happen to PZR heaters on a LT-110X failure low if RCN-HS-100-3 is selected to BOTH?
To Y?
All PZR heaters will deenergize on <25% Lvl interlock.
Nothing.
What will occur on a loss of NNN-D11 with respect to Pressure and Level control?
NNN-D11
LIC-110 Master level controller loses pwr = output fails to 0; LCVs fail closed = LD lost
Normal and Stby CHG pps off, manual control available
“Y” level and pressure control channels lose pwr and output fails to 0
“Y” htr cutout channel fails = All htrs off if selected to Both or “Y”
Select channel “X” on HS-110 (level), HS-100-3 (level cutout), and HS-100 (pressure)
What will occur on a loss of NNN-D12 with respect to Level and Press control?
NNN-D12
TS-224-2 pwr loss causes 523 to close = LD lost
TIC-223 fails to 0 causing TV-223 to close
PIC-201 fails to 0 output = BPCVs close = LD lost
PIC-100 Master pressure controller loses pwr = output fails to 0
PIK-100 Spray controller loses pwr = output fails to 0 = spray valves close
“X” level and pressure control channels lose pwr (not LTs/PTs) and output fails to 0
“X” htr cutout channel fails = All htrs off if selected to Both or “X”
Select channel “Y” on HS-110 (level), HS-100-3 (level cutout), and HS-100 (pressure)
What happens to PPCS when the selected PZR press fails low?
What will be the PPCS response to a selected PT that fails HIGH?
What will happen to PLCS/PPCS on a loss of NKN-D41?
Alpha train non class heaters will lose control power.
What will happen to PLCS/PPCS on a loss of NKN-D42?
What will happen to PLCS/PPCS on a loss of PKA-M41?
IAA-UV-2 fails closed which will cause a loss of the following:
Additionally, Aux spray valve 205 fail closed on LOP
AUX SPRAY IS NOT LOST.
Explain what happens on a TC/TH instrument failing HI at 100% power?
TC fails high, 100% power:
High Tave signal sent to PLCS resulting in maximum level setpoint.
No effect, PZR level already at maximum program value.
Operator selects unaffected Tave.
What will happen when a TC/TH instrument fails HIGH at 15 % power?
TC fails high, 15% power:
High Tave signal sent to PLCS resulting in maximum level setpoint.
“Pressurizer Trouble” annunciator alarms.
Letdown flow to minimum.
Operator takes local control of PLCS and shifts Tave to the unaffected
parameter.
What happens if a TC/TH instrument fails low at 100% power?
TC fails low, 100% power:
What will happen on a TC/TH instrument failure LOW at 15% power?
TC fails low, 15% power:
How will a failure of PNA-D25/ PNB-D26 affect PLCS and PPCS?
Panel PNA-D25 (PNB-D26)
PZR level transmitter RCA-LT-110X (RCB-LT-110Y) loses power / fails low.
All PZR heater breakers open if selected to the affected channel or “both” on RCN-HS-100-3.
Letdown to minimum if selected to the affected channel on RCN-HS-110.
Standby charging pump starts if selected to ‘X’ (‘Y’) channel on RCN-HS-110.
Operator will need to select channel ‘Y’ (‘X’) on RCN-HS-110 to restore PZR level control.
Operator will need to select channel ‘Y’ (‘X’) on RCN-HS-100-3 to restore PZR heater control.
What will happen to the PPCS and PLCS system on a loss of NNN-D11?
What happens to the PLCS and PPCS on a loss of NNN-D12?