What is the purpose of the Fire Detection System?
How many fire protection zones are there in the plant?
There are 238 fire protection zones in the plant
What component receives an input from the fire detectors?
The Fire Alarm Control Panels(FACPs) receive input from the fire detectors and provide an input to the Fireworks Control Consoles.
How many Fire Alarm Control Panels are there, and what component do they provide an input to?
Where are fire alarms displayed?
2. Fireworks Control Consoles
What are the Fire Alarm Control Panels equipped with for an emergency source of power?
The FACPs have an internal battery backup capable of providing power for 24 hours
What is advantageous of the Fire Alarm Control Panels configuration?
The FACPs are configured in such a way that any FACP can provide the status of any other detector or FACP connected in the loop.
Where are the power supplies to the Fire Alarm Control Panels?
1KXPB and 2KXPB
Where are the Fireworks Control Consoles located?
The Control Room
What is the power supply to the Fireworks Control Consoles?
#1 Console - 1KXPB(primary), auto swaps to 2KXPB(backup) #2 Console - 2KXPB(primary), auto swaps to 1KXPB(backup)
What are the events and the associated colors displayed on the Fire Control Consoles?
Alarms(red events)
Trouble(yellow events)
alarms have to be acknowledged on both consoles to allow another alarm to flash on the consoles
What are the four major screens on the Fire Control Consoles?
What affect does an abnormal state have on the Fire Control Consoles?
When a Fire Alarm Control Panel comes into an abnormal state the Fire Control Console screen will automatically change to the Annunciator Response Screen.
What are the indications on the Map Screen of the Fire Control Console?
Where can alarms be read on the Fire Control Consoles?
Alarms can be read from:
What are the color codes for alarms received on the Fire Control Console?
What are the types of fire detectors that are utilized in the Fire Detection System?
What is the design/purpose of the 4D Multisensor Detectors?
1. Contains 3 fire sensing elements: A. Ionization B. Photoelectric C. Heat 2. Most detectors are this type, but the Containment detectors were not replaced
Where is it useful to use ionization elements?
Ionization elements are suited for electrical fires where smoldering proceeds flames
Where is it useful to use Photoelectric Elements?
Photoelectric elements are useful in high humidity areas
What is the design/purpose of the Ultraviolet Flame Detectors?
Where are Ultraviolet Flame Detectors normally used?
What are the two types of Thermal Detectors?
2. Rate-of-rise
What are the two categories of Thermal Detectors?
2. Restorable