What are the FRVS fan initiation signals?
What are the power supplies for the 6 FRVS recirc fans?
2 fans each on A and B channel 1E AC and 1 fan each on the C and D 1E AC buses.
What are the FRVS recirc fan trips?
What is the series of events for FRVS initiation?
What is the LOCA/Hi Rad Actuation sequence for FRVS?
What does swapping control to the RSP do to FRVS?
Transfer to RSP opens Secondary Containment isolation dampers
What does it mean if the FRVS recirc fan pushbutton is flashing?
FRVS Recirc fan pushbuttons will flash if a start signal was received and the fan is not running.
What are FRVS fans rated for?
FRVS Recirc fans are rated at 30,000 scfm
What will a closure of the GUD-925(reactor building supply damper) cause?
caused the supply fans to trip and will cause reactor building d/p to degrade
How do you start an FRVS fan in non-emergent conditions?
What FRVS special features exist?
C & D SACS Cross Tie Capability
E & F Auto Restart Capability
A - D - Start 6 Seconds after LOCA
E – F – Start 17 Seconds after LOCA
Auto Lead Vent Fan – 19 seconds