What is the purpose of RBVS and how does it accomplish this?
Maintains dP to minimize ground level release, not necessarily for accident conditions i.e. 10 CFR 100
Provides negative dP to ensure leakage is always into the building.
RBVS provides a complete exchange of 1 volume of Rx building air per hour
Where are the RBVS room coolers located?
Room Coolers (2 per room)
1. HPCI, RCIC, RHR, Cores Spray (all cooled
by SACS)
2. SACS Room (Cooled by Control Room
Chilled Water AP400/BP400)
3. Steam tunnels (normally cooled by
chilled water, can be cross tied to RACS)
What do the RBVS duct heaters keep the various room temperatures at?
how does the RBVS fan trips/isolations remove power and how is power resored?
RBVS fans trip and dampers isolate (trips the 1E breaker [in the field] which indirectly feeds the RBVS supply and exhaust fans, must be locally reset AND started at breakers [1E swgr pistol grip switches])
What are the RBVS fan trip and damper isolation setpoints?
What prerequisites must be met before re-shutting a tripped RBVS 1E Breaker?
To reclose the 1E breaker, all initiating signals must be clear and
PCIS reset; then, the breaker must be manually reclosed at the
480V USS. (Top breakers on 10C650)
Describe RBVS and RBVE fan auto start operations and interlocks.
When do the RBVS steam leak dampers close?
Close on room high temperatures