When performing a visual inspection:
Fill in the blanks:
Cables must be correctly selected for their application, ____ carrying capacity and volt-____.
When performing a visual inspection:
True or false:
You should check that the accessories used are suitable for their purpose.
True.
Pretty obvious really.
When performing a visual inspection:
What must be checked when inspecting the protective & switching devices?
That they are correctly rated.
When performing a visual inspection:
True or false:
Damage can be ignored.
False.
Are you on beef?
When performing a visual inspection:
What must be checked regarding CPCs?
Assuming you are using twin & earth
That they are all correctly sleeved with green & yellow sleeving.
When performing a visual inspection:
Fill in the blanks:
All terminations must be ___ and ___ sound
When performing a visual inspection:
True or false:
Signage and information need not concern you.
False. This must be correct and placed in the appropriate places.
Ya berk.
True or false:
You can use anything to perform a voltage test.
False.
A voltage test must be performed using a device which conforms to GS38.
You mad bitch.
When do electrical installations need to be inspected and tested?
Where would one find recommended timescales for this?
At appropriate intervals during its lifetime.
Recommended timescales can be found in IET Guidance Note 3 (supporting BS7671).
When inspecting an installation…
Regarding conductors, what must be inspected?
When inspecting an installation…
Regarding connection, what must be inspected?
When inspecting an installation…
What must be checked in regards to shock protection?
When inspecting an installation…
What must be present in regards to protection against thermal effects?
When inspecting an installation…
What must be present in regards to protective devices?
When inspecting an installation…
What must be present in regards to access to information and equipment?
When inspecting an installation…
True or false:
You do not need to look at the connection of the conductors.
False.
This is pretty important.
theWhen inspecting an installation…
True or false:
You need to be able to identify the conductors.
True.
Pretty self explanatory really.
What is the width of a safe zone?
What is a safe zone?
The width of safe zones is 150mm.
Safe zones (or permitted zones) are areas where you are required to run cables through walls, as they are areas which aren’t as likely to be nailed or interfered with.
What is the minimum depth that cables must be run when installing cables in floors or ceilings?
More than 50mm.
Any less than this and the nail could potentially pierce the cable and it would become live.