There are five ‘dead’ tests listed below, place them in the correct order:
* Continuity of CPCs
* Insultation Resistance
* Polarity
* Mains voltage/ Safe isolation
* Continuity of ring final circuit conductors
The correct order of ‘dead’ tests is as follows:
1. Safe isolation
2. Continuity of CPCs
3. Continuity of ring final circuit conductors
4. Insulation resistance
5. Polarity
True or false:
Functional testing of RCDs can be done at any time in the testing order.
False.
This test must be done after establishing that the Earth Fault Impedance of the circuit is low enough to satisfy requirements in order for the RCD to be tested.