PGS Flashcards

(12 cards)

1
Q

What signal will cause auto closure of the PGS containment isolation valves, PGS*CV8046 & CV8028?

A

CIA

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What will cause a running primary grade water supply pump (PGS-P1A/B) to trip?

A

low suction pressure

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What is not function of the primary grade water system?

A

provide makeup to the charging pump cooling system

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

From where can PGS storage tank heating circulating pump 3PGS-P2A be remotely started?

A

reactor plant sampling panel

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

Nitrogen sparring of a primary grade water storage tank will remove which impurity?

A

oxygen

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Primary grade water system containment isolation valves function to isolate the primary grade water header inside containment upon receipt of what signal?

A

containment isolation phase A

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

The function of the primary grade water system supply pumps is to:

A

maintain constant system pressure to the primary water header

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

the primary grade water system supply pumps may be remotely started from which location?

A

Unit 3 control room

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

What describes the purpose of the primary grade water system?

A

supplies makeup and flushing water throughout the reactor plant

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

When the reactor plant is above 200F, the primary grade water system shall be in operation and able to supply internal water spray in:

A

pressurizer relief tank

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

The PGS system provides warm makeup water to:

A

CVCS system for boric acid batching operations

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

What shall not be operated when PGS tank level is below 15,000 gallons?

A

PGS pumps and heater loops

How well did you know this?
1
Not at all
2
3
4
5
Perfectly