SMP Flashcards

(4 cards)

1
Q

Why is an oil/water separator required to be filled with water prior to restoring it to service from maintenance?

A

as the separator fills from drains, the oil-water mixture would flow into the effluent compartment allowing oil to discharge

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

The Aux Boiler oil/water separator clean water effluent is released to the environment via:

A

submersible pump to the Aux Boiler blowdown tank drain tank

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

Where do the Millstone U3 Underdrains Sump Pumps outside the Emergency Diesel enclosure building discharge to?

A

Long Island sound via the yard storm drains

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What is the maximum flow rate allowed through the Turbine Building oil/water separator?

A

100 GPM

How well did you know this?
1
Not at all
2
3
4
5
Perfectly