What is the purpose of the Shield Cooling System
Designed to maintained structural concrete temperature less than 165 F, preventing weakening of the concrete due to moisture loss
When is the Shield Cooling System required to be in service?
When PCS temperature > 165 F
What is required if concrete temperature can’t be maintained below 165 F?
Commence a controlled plant shutdown
What are the power supplies for P-77A/B, Shield Cooling Pumps
P-77A - MCC-2
P-77B - MCC-1
What are the control room controls for the shield cooling pumps?
What is the low discharge pressure alarm setpoint for the shield cooling pumps?
35 psig
How many shield cooling coil sets are there?
2 (A and B)
How many coils are in each shield cooling coil set?
1 floor slab coil and 3 wall coils
What are the shield cooling temperature and flow alarms?
120 F
80 gpm
CV-0932/0934, Coil Inlet Supply Valves, design features
Shield Cooling Surge Tank design features
CV-0939, Shield Cooling Containment Isolation Valve
- Normally closed to isolate makeup water from the tank, because CV-0927, Surge Tank Makeup Valve, leaks by
How are chemicals added to the Shield Cooling System?
Chem add tank on east mezzanine is no longer used. Sodium Nitrite is added directly to the tank