Chapter 4 Cards Flashcards

(58 cards)

1
Q

Name the terms to describe telecom spaces

A

Er, tr, ef, te

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

How much clearance do racks in an equipment room need between them

A

1m or 3.3 ft

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What should you do if an equipment room layout hasn’t been provided?

A

Prepare one for approval before beginning work

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

Where Conduit ends should be positioned adjacent to?

A

To the left side of the back board if there’s a single piece of plywood

Or

In the left most corner of the room where multiple sheets of plywood are installed around perimeter walls of the room

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

For ICT systems what grade of plywood should the back board be?

A

A/C grade with the A side exposed to the interior of the tr and the C side is placed against the building structure or cabinet wall

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

What height about the finished floor should you start mounting the plywood at?

A

150mm or 6 inches

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

How many coats of fire retardant paint is required if the plywood isn’t already coated?

A

Two coats of fire retardant paint

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

What dimensions should plywood sheets used for backboards be installed at?

A

150mm or 6 inches above finished floor( aff) and with an installed height of 8.5 ft

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

When installing plywood backboards how much longer than the depth of the wall should the galvanized screws be?

A

12.7 mm or .5 inches liner than the depth of the wall covering including the plywood.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

What size should your toggle bolts be if you have to use them while installing plywood backboards…

A

A minimum of 6.3 mm or .25 in and must be good enough in length to allow the toggle to seat behind the framed wall after installation

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

What should a finished backboard installation look like?

A

It will look flush with counter sunk screws to avoid splitting the board

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

How far should toggle bolts be separated in a back board installation?

A

2 inches from the edge of the plywood sheet an a max of 24 in centers

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

What are common installation and set up issues that floor or wall mounted cabinets and racks have

A

Attachment.
Bracing.
Design layout.
Cable routing and management.
Bonding and grounding( earthing).

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

When it’s required the top of the floor mounted rack must be connected to what?

A

The wall, support barriers, cable runway, or cable tray.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

What is one RMU equal to?

A

45mm or 1.75 inches

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

What is the minimum spacing equipment must have to be placed in racks?

A

1 rmu

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
17
Q

Where should labels be placed on cabinets and racks

A

At the top of them and centered between the sides

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
18
Q

What is generally recommended about the cabinets placement?

A

That they should be placed with one edge flush with the floor tile cut line to ensure that no unnecessary floor tiles are used and to minimize distance to reach under cabinets

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
19
Q

What are the four methods that can be used to secure cabinets or racks to the underfloor or permanent slab

A
  • attachment to metal struts that are captured below the floor by two or more access stringers
  • attachment to metal struts below access floor that are suitably attached to the permanent floor
  • attachment using threaded rod directly to the permanent floor
  • attachment to channel bases bolted to floor slab
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
20
Q

you shouldn’t adjust or shim an anchor point more than what amount?

A

.5inches or 13 mm

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
21
Q

What is the minimum amount of clearance is needed in every race way to allow cable bundles to lay properly?

A

2 inches minimum

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
22
Q

When foam matting is used as an underfloor pathway or containment how thick should it be?

A

A minimum of half an inch thick and fill the aisle between the floor pedestals

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
23
Q

When underfloor cable trays run in parallel and are stacked directly above each other what is the amount of clearance needed between layers of the tray

A

12 inches but no less than 6 inches

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
24
Q

Should d rings be used as a substitute for ladder rack or cable tray?

A

Definitely not

25
What does an ef typically contain?
The entrance transition point for ap or sp services to the building and several elements of telecom bonding and grounding infrastructure
26
What is the te dedicated to ?
The telecom function and related support facilities of a specific work group
27
Where should the tr be located on a floor?
It should be located on the same floor as the work group it serves
28
What kind of access should a te have?
It should be accessible but be restricted to people with keys to get into them
29
If a door is hinged how should the enclosure be mounted?
It should be mounted that the door swings open a minimum of 90 degrees or provides unobstructed access to the inside of the enclosure
30
How many non switched 120 vac/ 20 A branch circuits with a NEMA 5-20R duplex receptacle should be available in each TE
A minimum of 1 dedicated of the branch circuits should be available for each equipment cabinet or rack in a te
31
How many lux or foot candles should light be measured at within a TE
538 lux or 50 foot candles
32
What are examples of cabling support systems?
Plywood back boards, clamps, rings, and hangers Cable trays with supporting hardware Cable runway and associated hardware Conduits Enclosed cabling pathways J hooks
33
How far should you be from electric motors and transformers to reduce emi
1220mm or 48 in
34
How far should you be away from neon lamps to reduce emi
130mm or 5 inches
35
How far should you be from arc welders to reduce emi
31.5 inches or 800mm
36
What are the kinds of fasteners
Screws Bolts nuts and washers Specialty fasteners
37
What is a bridle ring?
A metal ring formed out of galvanized wire stock with one side open
38
Where should outlet boxes be located?
Next to a wall stud or frame member and it should be at least 4 in away from all other wall members
39
What size of threaded rod do heavy duty installations use
5/8 size rod
40
What is the size range that cable retaining posts are available in?
6 inches-12inch lengths to allow cables to be installed to a depth exceeding the cable runways
41
Where should supporting attachments be applied on a cable tray?
Not more than 2 ft from the end of each side of a joint between two sections. Additional supports are required every 5ft thereafter
42
What is a fish tape?
A steel or fiber glass wire rigid enough to be pushed through conduit or in longer runs to a pull box
43
What are the air propelled devices used to run pull string?
A vacuum and a compressed air bottle or mechanical blower
44
What’s the first step of placing pull string in conduit with a fish tape?
Determine length of fish tape required and after estimating add a few feet to each run to make sure you have enough fish tape
45
Is the poke through method a recommended as a horizontal cabling solution
No there is a lot of draw backs to this method
46
When are floor openings for poke-thru devices performed?
They’ll be performed either during the floor construction for a new building by a gc or by a speciality contractor in an existing building
47
What is the max amount of cables open top cable supports should be used for
50
48
How should open top cable supports be installed
They should be attached to the buildings structure and installed on a center spacing of 4-5 feet.
49
How much clearance should open top supports be installed to have between the cabling and cable supports
A minimum of 3 inches
50
What are the two types of couplings used to join emt together
Compression and set screw
50
To avoid damaging the jacket how should ent be fastened
It should be securely fastened every 35.4 inches so it doesn’t bend when pulling cable
51
How much length should FMC runs be limited to if it’s needed to be used
20 ft and increase the conduit diameter by one trade size.
51
Should conduit bodies designed to handle electrical wiring systems be used in telecom cabling
Absolutely not
52
How many 90 degree bends are allowed in any one conduit segment?
No more than two 90 degree bends are allowed.
53
When might a third 90 degree bend in a single conduit segment be acceptable
If any of these things happen: The run doesnt exceed 33 ft The conduit size is increased to the next trade size If one of the bends is located within 12 in of the cable feed end. ( this exception applies only to placing operations where cable is pushed around the first bend)
54
What size range are hand benders allowed to bend?
1/2 trade size up to 1 1/4 trade size
55
What are the required bend radius rules when installing conduit?
If conduit is over 2 in. (53 mm), the bend radius must be 10× the internal diameter. If it is 2 in. (53 mm) or smaller, the bend radius must be at least 6× the internal diameter.
56
When optical fiber cable is being used how many inner ducts should you use and what sizes should they be?
3 inner ducts Two at 1.5 in and one at 1 in inside conduit designed for this purpose.