Fire Code 2023 Flashcards

(104 cards)

1
Q

The provisions of this section (Appendix Chapter 4) shall apply to _ hour care facilities in a Group R- occupancy licensed by a governmental agency.

A

24

This refers to the specific fire code requirements for certain care facilities.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

Special Requirements, Occupancy: R-3 Non-Ambulatory Patient - 6 or less Clients, Two stories max or not more than 3,000 sq feet contact Fire Authority within ______ hours of admission.

A

48

This is the time frame for notifying the Fire Authority regarding bedridden clients.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

Clients who become bedridden as a result of a temporary illness: A temporary illness is an illness which persists for ______ days or less.

A

14

This defines the duration for which a client can be considered temporarily ill.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

A bedridden client may be retained in excess of the ______ days upon approval by the Department of Social Services.

A

30

This allows for flexibility in housing bedridden clients beyond the standard duration.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

Group R-4 occupancies, where non-ambulatory clients are housed above the first story and there is more than 3,000 square feet of floor area above the first story shall be constructed of not less than ______ hour fire-resistance-rated construction throughout.

A

1

This specifies the fire-resistance requirements for certain Group R-4 occupancies.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Special Requirements, Occupancy: Group R-3.1 - Hallway Doors leading to Bedrooms shall be ______ automatically closing or by smoke detector activation.

A

1 3/8”

This measurement pertains to the specifications for hallway doors in Group R-3.1 occupancies.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

Special Requirements, Occupancy: School Facilities for Kindergarten Through 12 Grade: Exit Discharge shall be ______ foot wide.

A

20

This defines the minimum width for exit discharges in school facilities.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

Minimum clear width, Corridor: Group R-2.1 occupancies shall have ______ inches on floors housing non-ambulatory clients and ____ inches on floors housing ambulatory clients.

A

60 & 44-44

This is the required corridor width for non-ambulatory clients in Group R-2.1 occupancies.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

Group R-4 occupancies shall have ______ inches on floors housing clients.

A

44

This specifies the corridor width for Group R-4 occupancies.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

Group R-2.1 and Group R-4 occupancies housing more than ______ non-ambulatory clients above the first floor shall be provided with two vertical exit enclosures.

A

6

This indicates the threshold for requiring additional exit enclosures.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

Residential Care for the Elderly facility serving Alzheimer clients may be fenced and gates therein equipped with locks, provided safe dispersal areas are located not less than ______ feet from the buildings. dispersal areas shall be size to provide an area not less than__square feet per occupant. 

A

50 & 3

This ensures safety measures for facilities serving Alzheimer clients.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

Dispersal areas shall be sized to provide an area of not less than ______ square feet per occupant.

A

3

This specifies the minimum space requirement for dispersal areas.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

Special Requirements, Occupancy: Day Care Facilities - Under age 7 or containing more than 12 children per story shall not be located above the ______ floor.

A

4th

This regulation is aimed at ensuring safety for young children in day care facilities.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

Special Requirements, Occupancy: Large Family Day-Care Home: Not less than ______ days prior to date decision will be made on application, the zoning administrator shall mail ___ radius of exterior boundaries of proposed family care home.

A

10 & 100’

This outlines the notification period for zoning administrators regarding family care homes.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

“Property owners within [X] feet of the exterior boundaries of a proposed family care home shall be notified.”

A

100

This specifies the distance for notification related to family care home applications.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

Group E occupancies shall front directly on a public street or an exit discharge not less than _______ feet wide.

A

20

The exit discharge to the public street must be unobstructed and maintained only as access to the public street.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
17
Q

According to Appendix Chapter 4, RCFE equals?

A

Residential Care Facilities for Elderly

Also referred to as Residential Care For Elder.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
18
Q

RF and RCRE are regulated pursuant to?

A
  • State Fire Marshal
  • California Health and Safety

Both A & B are applicable.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
19
Q

R-4: Safety Padding shall comply with?

A
  • State Fire Marshal
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
20
Q

R3.1 - Ambulatory with 50 or more: Corridors and Aisles shall be a minimum of _______ inches?

A

44
## Footnote

This is the minimum width requirement for corridors and aisles.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
21
Q

The State Fire Marshal shall adopt separate building standards specifically relating to fire and life safety in Family Daycare Homes, which is Title _______ of the California Code of Regulations.

A

24

This title outlines specific standards for Family Daycare Homes.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
22
Q

Special Requirements, Occupancy: Large Family Day-Care Home: One _______ extinguisher is required.

A

2A10BC

This is the type of extinguisher mandated for large family day-care homes.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
23
Q

Fire Department Access Roads shall support _______ Thousand Pounds.

A

75

This weight capacity is necessary for safe access.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
24
Q

Fire Department Access Roads shall comply with?

A
  • California Fire Code

Compliance with these codes is essential for safety.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
25
Minimum Road width with a Hydrant is _______ feet, exclusive of shoulder.
26 ## Footnote This width is required for safe access to hydrants.
26
Fire Department Access Roads: Maximum grade is limited to _______%. Greater is approved by the Chief.
10 ## Footnote This maximum grade ensures safe access for emergency vehicles.
27
Dead end Road in excess of _______ feet must have turn around provisions.
150 ## Footnote This requirement is to ensure emergency vehicle access.
28
Fire Department Access Roads: Access Gates shall be a minimum of _______ feet and swing or slide open no less than 12 feet wide
20 ## Footnote Gates must swing or slide open for access.
29
Fire Department Access Roads: Divided Roadways with Fire Department gates shall open no less than _______ feet.
12 ## Footnote This width is necessary for safe access.
30
Fire Department Access Roads: Locked gates and fences and/or Electric Gates shall only be installed if approved by?
Fire Code Official ## Footnote Approval is required to ensure compliance with safety regulations.
31
Fire Department Access Roads: Dead end streets shall not exceed _______ feet.
750 ## Footnote If in excess, a permit is required.
32
Fire Department Access Road Signs: Signs shall be _______ wide and _______ height.
12 x 18 ## Footnote Red letters on white background.
33
Fire Department Access Roads: Access Gates shall be _______.
Manual ## Footnote Either A or B.
34
Buildings _______ feet in height or _______ stories shall provide two means of Fire Apparatus access.
30 - three ## Footnote This ensures adequate access for fire services.
35
Fire Department Access Roads: Maximum grade is limited to _______. Greater is approved by?
10% ## Footnote Greater is approved by the Fire Marshall.
36
Fire Department Access Roads: Projects having more than _______ dwelling units provide 2 separate roads.
200 ## Footnote Exception: Sprinkler increases to dwellings.
37
Buildings _______ sq feet in Area shall have two separate fire access roads placed a distance apart equal to not less than one half on the length of the max overall diagonal dimension of the lot.
62,000 ## Footnote This ensures adequate access for emergency services.
38
Fire Department Access Roads: Projects having more than _______ dwelling units provide 2 separate roads.
200 ## Footnote This is a requirement for safety.
39
Aerial Access: Vertical distance between grade & highest roof level exceeds _______ feet, an approved Aerial Road is required.
30 ## Footnote This is crucial for aerial firefighting operations.
40
Aerial Access: Aerial Access width shall be a minimum of _______ feet.
26 ## Footnote This width is necessary for fire apparatus maneuverability.
41
One or two Family dwelling residential developments where the number of dwelling units exceeds _______ shall be provided with two separate and approved fire apparatus access roads.
30 ## Footnote This is to ensure adequate access for fire services.
42
Explosives: There are _______ different Explosive Divisions.
6 ## Footnote Each division categorizes the level of hazard.
43
Explosives: Division _______ are a Minor Explosive Hazard.
1.4 ## Footnote This division includes materials that pose a lower risk.
44
Explosives: Division _______ are a High Explosive Hazard.
1.1 ## Footnote This division includes materials that pose a significant risk.
45
Fire department access road signs; signs shall be 12 inches wide 18 inches height, ___ letters on_____
Red - white
46
What is the classification of **Explosives**?
1.6.
47
Which of the following is **not** included in **Compressed Flammable gases**? 1. Methane 2. Acetylene 3. Carbon monoxide
Oxides of Nitrogen ## Footnote Compressed flammable gases have a boiling point at or above 100 F.
48
Flammable Class **1B** have a Flash Point below _______.
73 F ## Footnote This classification indicates a specific range for flammable materials.
49
Class **IIIA** have a Flashpoint at or above 140 F and below _______.
200 F ## Footnote This class includes certain combustible liquids.
50
A Class **II** liquid is classified as a?
Combustible ## Footnote This classification is important for safety regulations.
51
Class **IIIB** have a Flashpoint at or above _______.
200 F ## Footnote This class includes specific types of combustible liquids.
52
Solid Oxidizer, Organic Peroxides and Unstable Reactive Material are categorized in _______ Classes.
4 ## Footnote These materials require careful handling due to their reactive nature.
53
Organic Peroxides have _______ Classes.
5 ## Footnote This classification indicates their hazardous properties.
54
Unstable Reactive Material have _______ Classes.
4 ## Footnote This classification is crucial for safety management.
55
Water-Reactive Material have _______ Classes.
3 ## Footnote These materials can react violently with water.
56
Specific gravity is the weight of a liquid compared to _______.
Water ## Footnote This measurement is important for understanding liquid properties.
57
Vapor density is the weight of a gas compared to _______.
Water ## Footnote This measurement helps in assessing gas behavior in the environment.
58
A _______ HMIS shall be provided for each building, including its appurtenant structures.
Separate ## Footnote This ensures proper hazardous material management.
59
Haz Mat Inventory Statement (HMIS): Any changes to the HMIS provide within _______ days.
30 ## Footnote Timely updates are essential for safety compliance.
60
Haz Mat Inventory Statement (HMIS): Site plan should include land use within _______.
1 mile ## Footnote This distance is critical for safety assessments.
61
Hazardous Material Management Plan (HMMP) 'Short Form': A facility shall qualify as a minimal storage site if the quantity of each hazardous material stored is _______ pounds or less for solids.
250 ## Footnote This limit helps define minimal storage requirements.
62
Hazardous Material Management Plan (HMMP) 'Short Form': A facility shall qualify as a minimal storage site if the quantity of each hazardous material stored is _______ gallons or less for liquids.
55 ## Footnote This limit is important for regulatory compliance.
63
Hazardous Material Management Plan (HMMP) 'Short Form': A facility shall qualify as a minimal storage site if the quantity of each hazardous material stored in one or more facilities in an aggregate quantity for the facility is __ pounds or less for solids, 55 gallons or less for liquids, or 200 ft.³ or less at NTP for compressed gases 
500
64
The permittee shall develop and follow a written **inspection procedure** acceptable to — for inspecting the facility for events or practices which could lead to unauthorized discharges of hazardous materials.
The Chief ## Footnote This procedure is essential for maintaining compliance with hazardous material regulations.
65
The **Hazardous Material Management Plan (HMMP) 'Short Form'** is required when compressed gas is _______ cubic feet or less.
200 ## Footnote This specifies the threshold for requiring a short form of the HMMP.
66
The **Hazardous Material Management Plan (HMMP) General Facility Description (Site Plan)** requires a site plan on paper, showing the location of all buildings, structures, and chemical loading areas. The drawing must indicate approximate scale, northern direction, and date completed. The paper size should be _______.
8 ½ x 11 ## Footnote This size is standard for official documentation.
67
The **Hazardous Material Management Plan (HMMP)** requires listing all special land uses within _______ mile.
1 ## Footnote This helps in assessing potential impacts on hazardous material management.
68
Evaluation of **Hazard**: Physical properties, such as whether a material is a solid, liquid, or gas at ordinary _______ and _______ are considered along with chemical properties.
Temp and Pressures ## Footnote These factors determine the requirements for containment of hazardous materials.
69
Hazardous materials inventory statements and hazardous materials management plans shall be maintained by the permittee for a period of not less than _______ years after submittal of updated or revised versions.
3 ## Footnote These records must be available to the fire chief upon request.
70
True or false: A smoke detector is in violation if painted.
TRUE ## Footnote Painting a smoke detector can impair its functionality.
71
Fire Protection Systems - Non-Compliant Conditions: Replace water and air pressure gauges that have been installed more than _______ years.
5 ## Footnote Regular maintenance is crucial for fire protection systems.
72
Fire Protection Systems - Non-Compliant Conditions: Hose Cabinet Racks shall be cited if the rack is incapable of swinging open at least _______ degrees.
90 ## Footnote This ensures accessibility in emergencies.
73
Fire Protection Systems, Fire Pump - Non-Compliant Conditions: Cite if Diesel Fire Pump Tank is less than _______.
2/3 ## Footnote Adequate fuel levels are necessary for fire pump operation.
74
Haunted houses, ghost walks, and similar amusement uses shall only be located in structures that comply with the provisions for **Special Amusement Areas** in accordance with the California _______ Code.
Building ## Footnote Compliance with building codes ensures safety in amusement structures.
75
Temporary Haunted House, Exits: Two exits must be provided if occupant load is _______ or more.
50 ## Footnote This is a safety requirement for crowd management.
76
Temporary Haunted House: Illuminated exit signs shall be provided at each exit serving an occupant load of _______ or more.
50 ## Footnote Proper signage is crucial for safety in emergencies.
77
Exit doors serving an occupant load of **_ or more** shall not be provided with a latch or lock unless it is panic hardware.
50 ## Footnote This regulation ensures that exit doors are easily operable in emergencies.
78
Haunted houses and ghost walks shall be provided with **fire protection systems**. Exception: When the total floor area is less than _______ square feet. Travel distance to exit less than ___ feet
1,000 & 50 ## Footnote This exception applies if the travel distance to an exit is less than 50 feet.
79
Temporary Haunted House: Provide **2A20BC Extinguisher** every _______ feet of travel.
50 ## Footnote This ensures adequate fire safety measures in temporary structures.
80
Temporary Haunted House: Portable generator shall be no less than _______ feet from structures.
20 ## Footnote This distance helps prevent fire hazards associated with generators.
81
Temporary Haunted House: Extension Cords shall be?
Protected from foot traffic ## Footnote This minimizes tripping hazards and potential damage to cords.
82
Temporary Haunted House: Flame Retardants shall be Class _______ Rated.
A ## Footnote Class C flame retardants are suitable for use in environments with electrical hazards.
83
Temporary Haunted House: Are **Open Flame** Prohibited?
Yes ## Footnote Open flames pose significant fire risks in crowded or enclosed spaces.
84
Chief Reg #4: Standby System: Automatically energized from alternate on site electrical supply within _______ seconds of failure.
60 ## Footnote This ensures continuity of power for critical systems during outages.
85
Chief Reg #4: Public address system. A _______ way system providing communication from the building control station and required locations.
1 ## Footnote This allows for effective communication in emergencies.
86
Chief Reg #4: The Fire Department Voice Communication System is a _______ way system.
2 ## Footnote This facilitates communication between the fire department and building occupants.
87
Chief Reg #4: Emergency System: Automatically energized from alternate on site electrical supply within _______ seconds of failure.
10 ## Footnote Quick activation is crucial for emergency response systems.
88
Chief Reg #4: Class I Dry: _______ inch hose for LAFD trained to handle hose for occupant use until FD arrival.
1 ½ ## Footnote This size is standard for fire department use.
89
Chief Reg #4: Class II Wet: _______ inch hose.
1 ½ ## Footnote This size is typically used for smaller fire suppression needs.
90
Chief Reg #4: Class III Combined Wet: _______ inch outlets with Sprinklers.
1 ½ & 2 1/2 ## Footnote This configuration supports both sprinkler and hose systems.
91
Chief Reg #4: Combined system. The water piping both serves and supplies water for the automatic sprinkler system. The outlets for Fire Department use are _______ inch.
2 ½ ## Footnote This ensures adequate water supply for firefighting efforts.
92
The **Chief** shall be notified by the concerned building owner or his agent at least ______ working days in advance of the performance of any required test.
10 ## Footnote The exact number of working days is not specified in the provided text.
93
At the conclusion of each test, the Chief shall be notified within ______ hours of any fire protection equipment that was determined to be inoperable.
24 ## Footnote This ensures timely communication regarding the status of fire protection equipment.
94
When it is determined that any fire protection equipment is inoperable or defective, the owner or his agent shall commence repair of the deficiencies ______.
Forthwith ## Footnote This indicates the urgency of addressing any deficiencies in fire protection equipment.
95
Phase II - Override: Determine that the proper in-car switch is provided in each elevator car. The in-car switch shall be a two-position key-operated switch, keyed ______.
Identically with the designated main floor switch ## Footnote The key shall not be removable in the 'ON' position.
96
Smoke Control Systems shall provide not less than ______ exchanges of air per hour.
6 ## Footnote The exact number of air exchanges is not specified in the provided text.
97
One Year test intervals are required on all buildings containing all the following except ______.
fire protection assemblies
98
Hose Cabinet doors shall swing open a minimum of ______ degrees.
90 ## Footnote This ensures accessibility and functionality of hose cabinets.
99
Five Year test intervals are required on all buildings containing all the following except ______.
Elevators ## Footnote This indicates that elevators are not included in the five-year test interval requirement.
100
Class I - Dry Standpipe are Air Tested to ______ psi for leaks and Hydro tested not less than 50 psi greater than head pressure but not less than ______ psi.
25 - 150 ## Footnote This specifies the testing requirements for Class I Dry Standpipes.
101
One Year test intervals are required on buildings over 75 feet containing all the following except ______.
Refrigerator systems ## Footnote This indicates that elevators are not included in the one-year test interval requirement for taller buildings.
102
Five Year test intervals are required on buildings NOT over 75 feet containing all the following except ______.
Fire Escapes ## Footnote This indicates that fire escapes are not included in the five-year test interval requirement for shorter buildings.
103
Class III - Operate Fire Pump for 7 minutes at ______ % per listed rating. Follow the test with 3 minutes at 65% of rated PSI.
150 ## Footnote This specifies the operational requirements for testing fire pumps.
104
Dry Standpipe are Air Tested to ______ psi for leaks and Hydro tested not less than 50 psi greater than head pressure but not less than ______.
25 - 150 ## Footnote This reiterates the testing requirements for Dry Standpipes.