FIRE CODE CH. 9 Flashcards

(188 cards)

1
Q

Fire Protection Systems required by this code or the _______ shall be installed, repaired and maintained in accordance with this code.

A

California Building Code

This code outlines the standards for fire protection systems.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

The _______ shall have the authority to require construction documents and calculations for all fire protection and life safety systems.

A

Fire Code Official

This official is responsible for overseeing fire safety compliance.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

Fire Protection Systems - Maintenance Standards for Water Based and Portable Fire Extinguishers: In Accordance with?

A

California Title 19, Div. 1

This title provides regulations for fire safety equipment maintenance.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

Every fire alarm system or device, sprinkler system, fire extinguisher, fire hose, fire-resistive assembly or any other fire safety assembly is subject to?

A

California Title 19, Div. 1

This regulation governs the installation and maintenance of fire safety systems.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

Fire Protection Systems - Maintenance: If tested _______ days prior to next required service date, the invoice must bear a statement indicating the system was tested early.

A

30

This specifies the timeframe for early testing of fire protection systems.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Fire Protection System Testing shall be conducted in the presence of?

A

The Fire Code Official

This ensures compliance and oversight during testing.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

Persons shall not remove or modify any fire protection or life safety system without approval from the _______.

A

Fire Code Official

This regulation protects the integrity of fire safety systems.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

Fire Pump rooms shall have a minimum temperature of what degrees?

A

40

This temperature requirement helps maintain operational efficiency of fire pumps.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

Permanently installed _____ illumination shall be provided in the automatic sprinkler system riser and

A

Artificial

This ensures visibility and safety in critical areas.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

Fire Protection System testing shall be performed by those licensed in accordance with Health and Safety Section 13196.5. Exception: _______ may waive, in writing, Fire Departments to conduct testing and maintenance.

A

State Fire Marshal

This exception allows for flexibility in testing requirements.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

California Code of Regulations, Title 19, Division 1, Inspection Requirements. A license to _______ inspections may be conducted by any person designated by the building owner. Who gives exceptions

A

perform & state fore marshal

This regulation allows designated individuals to conduct inspections based on their training.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

A license ____ to perform inspections

A

Shall not be required .

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

High-rise buildings must comply with NFPA 4 for integrated testing, with tests performed at intervals not exceeding _______ years.

A

10

Unless otherwise specified by an integrated system test plan prepared in accordance with NFPA 4.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

Records of all inspecting, testing, and maintenance shall be retained on the premises for a period of _______ years after the next required test or maintenance.

A

5

This is the retention period mandated for records by the building or system owner.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

When a required fire protection system is out of service, the Fire Department and Fire Code Official shall be notified immediately and a _______ shall be provided for all occupants left unprotected.

A

Fire Watch

This is required until the fire protection system has been returned to service.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

The Fire Code Official is authorized to permit the removal of existing occupant-use hose lines under what two conditions?

A
  • The hose line would not be utilized by trained personnel or the fire department
  • The remaining outlets are compatible with local fire department fittings

These conditions ensure safety and compliance with fire regulations.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
17
Q

A _______ shall be used to indicate that a system, or portion thereof, has been removed from service.

A

Tag

This is a safety measure to inform personnel of the system status.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
18
Q

Sprinklers are required in all Group A-1, A-3, A-4, E, F-1, M, S-1, S-2 occupancies when the Fire Area is greater than _______ square feet.

A

12,000

This requirement is part of fire safety regulations for large occupancies.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
19
Q

Sprinkler Standpipe Inlet Signs shall be _______ inches.

A

8 × 4

This specifies the size for visibility and compliance.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
20
Q

Sprinkler Heads in Spray Areas shall be covered with cellophane bags having a thickness of _______ or less.

A

.003

Alternatively, they can be covered with a similar thickness paper bag.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
21
Q

Spare Sprinkler Heads are required when a building has 300 or less heads: _______.

A

6

This ensures that there are adequate replacements available.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
22
Q

Spare Sprinkler Heads are required when a building has over 1,000 heads: _______.

A

24

This is to maintain fire safety standards in larger buildings.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
23
Q

Sprinklers are required in basements when any portion is located more than _______ feet from an opening.

A

75

This requirement helps ensure adequate fire protection in basement areas.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
24
Q

Sprinklers are required in buildings 55 feet or more in height with an occupancy load of 30 or more. The water supply shall be capable of supplying the system for _______ minutes.

A

30

This is a critical requirement for fire safety in high-rise buildings.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
25
Rubbish Chutes require an auto sprinkler to be installed at the top and in the termination room, with additional heads on _______.
Alternating Floors ## Footnote This ensures proper fire protection throughout the chute.
26
Are **auto sprinklers** required for rubbish chutes?
Yes ## Footnote This indicates that safety measures must be in place for rubbish chutes.
27
According to NFPA __, what section requires that a building be equipped with an automatic sprinkler system?
NFPA 13 ## Footnote This standard outlines the requirements for sprinkler systems in buildings.
28
What is the minimum opening size for **exterior wall openings**?
30 inches ## Footnote This requirement ensures adequate ventilation and safety.
29
If a fire protection system is tested days prior to the next required service date, what must the invoice indicate?
The system was tested early ## Footnote This ensures proper documentation of maintenance activities.
30
Buildings ___’ in height or more require sprinklers. The water supply shall be capable of supplying the system for ______ minutes.
55’ 30 minutes ## Footnote This is a critical requirement for fire safety in taller buildings.
31
No sprinklers are required in bathrooms if they do not exceed ______ square feet.
55 ## Footnote This exemption helps reduce unnecessary sprinkler installations.
32
For buildings over **75 feet**, the secondary water supply must not be less than ______ gallons.
15,000 ## Footnote This ensures adequate water supply for fire protection systems.
33
Water supply for sprinkler systems shall be protected against ______.
Backflow ## Footnote This is essential to prevent contamination of the water supply.
34
A single combination water supply for residential sprinklers is allowed if the domestic demand is added to the sprinkler demand as required by NFPA __R
13R ## Footnote This standard pertains specifically to residential sprinkler systems.
35
All sprinkler calculations shall be per ______ requirements.
NFPA 13 ## Footnote This standard provides guidelines for sprinkler system design and installation.
36
Fire Protection Systems - Maintenance Standards for Water Based and Portable Fire Extinguishers are in accordance with ______.
California Title 19, Div. 1 ## Footnote This regulation outlines maintenance standards for fire protection systems.
37
Water Based Fire Protection Systems shall be inspected and tested in accordance with the frequencies required by NFPA ______.
25 ## Footnote This standard specifies inspection and testing protocols for fire protection systems.
38
Hose tread for sprinklers and FDC's is prescribed by ______.
Fire Code Official ## Footnote This ensures compliance with local fire safety regulations.
39
Security of **sprinkler supply valves** and controls shall be chained open with locks. Also include ______.
Tamper valve protection ## Footnote This measure prevents unauthorized access to critical fire safety equipment.
40
What is the minimum clearance required for **Sprinkler Standpipe Control**?
18 inches ## Footnote This clearance is necessary for proper operation and maintenance.
41
Sprinklerheads located in spray rooms must be protected from overspray residue. Bags shall be replaced _______.
Periodically ## Footnote This prevents excessive buildup of overspray on the sprinklerheads.
42
___ _____ official prescribes the fire hose threads and fittings used in connection with automatic sprinkler systems?
Fire Code Official ## Footnote This ensures compliance with safety regulations.
43
Floor control valves and waterflow detection assemblies must be installed at each floor where the highest story is more than ______ feet above the lowest level of fire department vehicle access.
30 ## Footnote This applies to buildings that are four or more stories in height.
44
Engineered and pre-engineered fixed extinguishing systems must be inspected, tested, and maintained as specified in ______.
California Title 19, Div. 1 ## Footnote This regulation outlines the maintenance requirements.
45
Alternate Sprinkler Systems, Wet Chemical Systems, and Dry Chemical Systems must be tested every ______ months.
6 ## Footnote Regular testing ensures the systems are functional and compliant.
46
Manual Activation Valves for Alternate Sprinkler Systems must be located near means of egress from the cooking area a minimum of 10 feet and a maximum of ______ feet from the kitchen exhaust system.
20 ## Footnote This distance is crucial for safety and accessibility.
47
High Pressure & Low-Pressure Cylinders for Alternate Sprinkler Systems must be refilled when the container shows a content loss of more than ______.
10 ## Footnote This ensures the systems remain operational.
48
Structures are required to be within 150 feet of a roadway. What is an exception?
Fully sprinklered ## Footnote Fully sprinklered buildings may have different access requirements.
49
No person shall operate, maintain, or use any automatic fire extinguishing system until a Final Inspection Tag of Approval has been issued by the ______.
Chief ## Footnote This approval is necessary for legal and safety compliance.
50
For Alternate Extinguishing Systems with Low Pressure Cylinders, the pressure gauge should be observed ______.
Weekly ## Footnote Regular checks help maintain system readiness.
51
System hoses for Alternate Extinguishing Systems shall be examined yearly and pressure tested every 5 years at not less than ______ PSI.
2,500 ## Footnote This testing ensures the integrity and safety of the hoses.
52
Where should **Manual Activation Valves** for Alternate Extinguishing Systems be located?
Near means of egress from cooking area, a minimum of 10 ft and a maximum of 20 ft from kitchen exhaust system ## Footnote This ensures accessibility and safety in case of fire emergencies.
53
A **Deep Fryer** up to 80 pounds requires how many gallons of Class K wet-chemical portable extinguish?
1 gallon ## Footnote This is a specific requirement for fire safety in commercial kitchens.
54
Who must test and approve **Standpipe Systems**?
The Chief ## Footnote This ensures compliance with safety regulations.
55
Does building management and occupants have to be notified of testing and maintenance of **Fire Protection systems**?
Yes ## Footnote Notification is crucial for safety and awareness.
56
Standpipe Systems are installed in accordance with **NFPA**?
14 ## Footnote NFPA 14 outlines the standards for the installation of standpipe and hose systems.
57
Class III Standpipes requirements include all the following except?
* Building 4 or more stories in height * Where floor level of the highest story is located more than 30 feet above the lowest level for Fire Vehicle Access * Where the floor level of the lowest story is located more than 30 feet below highest level of Fire Vehicle Access * 3 or more stories below highest-level Fire Vehicle Access ## Footnote These criteria define when Class III Standpipes are necessary.
58
Shopping Mall hose connection outlets shall be near each exit, within interior stairwells and every ______ feet?
200 ## Footnote This spacing is important for accessibility during emergencies.
59
Stages greater than ______ square feet shall be equipped with Class III with 1 ½" and 2 ½" outlets.
1,000 ## Footnote This ensures adequate fire protection for large assembly areas.
60
Helispots shall be provided with a Class ______ outlet?
3 ## Footnote This is a requirement for emergency helicopter landings.
61
The location of Class I hose connection outlet shall be provided for each story above and ______?
Below ## Footnote This ensures that hose connections are accessible from all levels.
62
Class I and Class II Standpipes are required to have ______ feet of hose attached.
100 ## Footnote This is a standard requirement for effective firefighting.
63
Class I and Class II Standpipes are required to provide a minimum of a ______ foot stream?
30 ## Footnote This ensures sufficient reach for firefighting efforts.
64
Standpipe Cabinet Identification requires ______ inch high color that contrasts indicating equipment in cabinet.
2 ## Footnote This helps in quickly identifying fire safety equipment.
65
When a Fire Protection System is 'Out of Service', management shall notify the **Fire Code Official**?
Immediately ## Footnote Prompt notification is essential for safety compliance.
66
What indicates that a Fire Protection System is 'Out of Service'?
Tag ## Footnote Tags are used to alert personnel of the system's status.
67
The **Fire Code Official** shall be notified in writing by the building when the recalled component parts have been replaced. Who is responsible for this notification?
Owner ## Footnote This ensures that the Fire Code Official is aware of any changes to recalled components.
68
Extinguishers are required within _______ of all cooking equipment?
30 feet ## Footnote This regulation helps ensure quick access to fire extinguishers in case of cooking-related fires.
69
Extinguishers are required in buildings under construction. They are to be located on what floor?
Each floor ## Footnote This ensures safety measures are in place on every level of the construction site.
70
Extinguishers that have a total weight of less than 40 pounds must be mounted not more than _______ above the ground.
5 feet ## Footnote This height regulation facilitates easy access to lighter extinguishers.
71
The number, size, placement, and limitations of use of extinguishers required shall be determined by using _______.
California Title 19, Div. 1 ## Footnote This title provides the legal framework for fire safety regulations in California.
72
Extinguishers and extinguishing agents for the protection of Class ______ hazards shall be of types approved for use on the specific combustible metal hazard.
D ## Footnote Class D extinguishers are specifically designed for combustible metal fires.
73
Water extinguishers can be used in an environment between _______ F and _______ F.
40 to 120 ## Footnote This temperature range ensures the effectiveness of water extinguishers.
74
When extinguishers are Hydrostatic tested, they shall be returned within _______ days.
30 days ## Footnote Timely return after testing ensures extinguishers remain available for use.
75
Portable Extinguisher ratings are based on Flammable or Combustible Liquids with depth less than or equal to _______ inch & where surface area is less than 10 sq. ft.
.25 inch ## Footnote This specification helps categorize the effectiveness of extinguishers on small liquid fires.
76
Extinguishers greater than 40 lbs must be top mounted not more than _______ above the floor but in no case the bottom be less than _______ inches from the floor.
3 ½ feet; 12 inches ## Footnote These mounting regulations ensure accessibility and safety.
77
Do not locate extinguishers where the temperature may exceed _______ degrees.
120 degrees ## Footnote High temperatures can compromise the integrity and functionality of extinguishers.
78
Class 'A' extinguishers are required every _______ feet of travel.
75 feet ## Footnote This distance ensures that individuals can quickly access extinguishers in case of a fire.
79
Class 'B' extinguishers are required every _______ to _______ feet of travel.
30 to 50 feet ## Footnote This range is specific to areas where flammable liquids are present.
80
Extinguisher Inspection Record: Manual inspection must include the initials of the person performing inspection on the tag or an inspection checklist maintained on file or an electronic system that provides a permanent record. Exception: electronically monitored inspections are done _______.
Monthly ## Footnote Regular inspections are crucial for maintaining fire safety equipment.
81
Are calcium chloride solutions allowed in stainless steel extinguishers?
Never ## Footnote This prohibition is due to the corrosive nature of calcium chloride on stainless steel.
82
High-Hazard class **'A' Occupancies** require a minimum _______.
1 extinguisher ## Footnote This is a safety requirement for high-hazard areas.
83
High-Hazard class **'A' Occupancies** require an extinguisher every _______ feet of travel.
75 ## Footnote This distance is set to ensure accessibility to fire extinguishers.
84
What is the maximum service area, in sq feet, for an extinguisher in an **'A' type Occupancy**?
11,250 ## Footnote This area is defined to ensure adequate coverage for fire safety.
85
Class **'B' Extinguisher table** requires a Class 'B' extinguisher max travel distance of _______ feet.
* 30 feet * 50 feet ## Footnote This varies based on the hazard level.
86
Fire extinguishers with a Class **'K' rating** shall be provided for hazards involving _______.
combustible cooking media ## Footnote The maximum travel distance shall not exceed 30 feet.
87
Type **'B' Occupancies** require _______ extinguishers of lower rating than found in California Code of Regulations, Title 19.
two or more ## Footnote This is to ensure compliance with safety regulations.
88
Portable fire extinguishers shall be provided for occupancies involving **combustible metals** classified as Class _______.
D ## Footnote This classification is specific to certain types of fires.
89
Two 2 1/2-gallon (9.46 L) water-type extinguishers can fulfill the requirement of one rated extinguisher of Class _______.
4A ## Footnote This is a specific rating for water-type extinguishers.
90
Fire Alarm System Drawings shall use **NFPA** symbols, specifically _______.
170 ## Footnote This standard ensures consistency in fire safety documentation.
91
Alarms are required for **Assemblages occupancy** of _______ or more.
1,000 ## Footnote This is a safety measure for large gatherings.
92
Are **Fire Alarms Required** in all Day Care occupancies?
Yes ## Footnote This is mandated for the safety of children.
93
Fire Alarms are required in all High-Rise buildings and Group R occupancies. What is the minimum requirement for Group **H, I and M** occupancies?
Manual pulls ## Footnote This ensures that occupants can alert authorities in case of fire.
94
Smoke Alarms and Detector Locations must not be within _______ feet of Bathrooms & HVAC supply registers.
3 ## Footnote This is to prevent false alarms and ensure proper functioning.
95
For tray-shaped ceilings (coffered ceilings), smoke alarms and smoke detectors shall be installed on the highest portion of the ceiling or within _______ inches vertically down from the highest point.
12 ## Footnote This placement is crucial for effective smoke detection.
96
High-Hazard class **'A' Occupancies** require a minimum _______.
1 extinguisher ## Footnote This is a safety requirement for high-hazard areas.
97
High-Hazard class **'A' Occupancies** require an extinguisher every _______ feet of travel.
75 ## Footnote This distance is set to ensure accessibility to fire extinguishers.
98
What is the maximum service area, in sq feet, for an extinguisher in an **'A' type Occupancy**?
11,250 ## Footnote This area is defined to ensure adequate coverage for fire safety.
99
Class **'B' Extinguisher table** requires a Class 'B' extinguisher max travel distance of _______ feet.
* 30 feet * 50 feet ## Footnote This varies based on the hazard level.
100
Fire extinguishers with a Class **'K' rating** shall be provided for hazards involving _______.
combustible cooking media ## Footnote The maximum travel distance shall not exceed 30 feet.
101
Type **'B' Occupancies** require _ or more extinguishers of lower rating than found in California Code of Regulations, Title 19.
2 or more ## Footnote This is to ensure compliance with safety regulations.
102
Portable fire extinguishers shall be provided for occupancies involving **combustible metals** classified as Class _______.
D ## Footnote This classification is specific to certain types of fires.
103
Two 2 1/2-gallon (9.46 L) water-type extinguishers can fulfill the requirement of one rated extinguisher of Class _______.
4A ## Footnote This is a specific rating for water-type extinguishers.
104
Fire Alarm System Drawings shall use **NFPA** symbols, specifically _______.
170 ## Footnote This standard ensures consistency in fire safety documentation.
105
Alarms are required for **Assemblages occupancy** of _______ or more.
1,000 ## Footnote This is a safety measure for large gatherings.
106
Are **Fire Alarms Required** in all Day Care occupancies?
Yes ## Footnote This is mandated for the safety of children.
107
Fire Alarms are required in all High-Rise buildings and Group R occupancies. What is the minimum requirement for Group **H, I and M** occupancies?
Manual pulls ## Footnote This ensures that occupants can alert authorities in case of fire.
108
Smoke Alarms and Detector Locations must not be within _______ feet of Bathrooms & HVAC supply registers.
3 ## Footnote This is to prevent false alarms and ensure proper functioning.
109
For tray-shaped ceilings (coffered ceilings), smoke alarms and smoke detectors shall be installed on the highest portion of the ceiling or within _______ inches vertically down from the highest point.
12 ## Footnote This placement is crucial for effective smoke detection.
110
High-Hazard class **'A' Occupancies** require a minimum _______.
1 extinguisher ## Footnote This is a safety requirement for high-hazard areas.
111
High-Hazard class **'A' Occupancies** require an extinguisher every _______ feet of travel.
75 ## Footnote This distance is set to ensure accessibility to fire extinguishers.
112
What is the maximum service area, in sq feet, for an extinguisher in an **'A' type Occupancy**?
11,250 ## Footnote This area is defined to ensure adequate coverage for fire safety.
113
Class **'B' Extinguisher table** requires a Class 'B' extinguisher max travel distance of _______ feet.
* 30 feet * 50 feet ## Footnote This varies based on the hazard level.
114
Fire extinguishers with a Class **'K' rating** shall be provided for hazards involving _______.
combustible cooking media ## Footnote The maximum travel distance shall not exceed 30 feet.
115
Type **'B' Occupancies** require _______ extinguishers of lower rating than found in California Code of Regulations, Title 19.
two or more ## Footnote This is to ensure compliance with safety regulations.
116
Portable fire extinguishers shall be provided for occupancies involving **combustible metals** classified as Class _______.
D ## Footnote This classification is specific to certain types of fires.
117
Two 2 1/2-gallon (9.46 L) water-type extinguishers can fulfill the requirement of one rated extinguisher of Class _______.
4A ## Footnote This is a specific rating for water-type extinguishers.
118
Fire Alarm System Drawings shall use **NFPA** symbols, specifically _______.
170 ## Footnote This standard ensures consistency in fire safety documentation.
119
Alarms are required for **Assemblages occupancy** of _______ or more.
1,000 ## Footnote This is a safety measure for large gatherings.
120
Are **Fire Alarms Required** in all Day Care occupancies?
Yes ## Footnote This is mandated for the safety of children.
121
Fire Alarms are required in all High-Rise buildings and Group R occupancies. What is the minimum requirement for Group **H, I and M** occupancies?
Manual pulls ## Footnote This ensures that occupants can alert authorities in case of fire.
122
Smoke Alarms and Detector Locations must not be within _______ feet of Bathrooms & HVAC supply registers.
3 ## Footnote This is to prevent false alarms and ensure proper functioning.
123
For tray-shaped ceilings (coffered ceilings), smoke alarms and smoke detectors shall be installed on the highest portion of the ceiling or within _______ inches vertically down from the highest point.
12 ## Footnote This placement is crucial for effective smoke detection.
124
For stairways leading up from a basement, smoke alarms or smoke detectors shall be located on the basement ceiling near the _______.
Entry to the stairs ## Footnote This placement is critical for early detection of smoke when exiting the basement.
125
Duct smoke detection. Smoke detectors listed for use in air duct systems shall be provided in accordance with the ______ ______ code
California Mechanical Code ## Footnote Compliance with this code ensures proper installation and functionality of duct smoke detectors.
126
Where a wired communication system is approved in lieu of an in-building, two-way emergency responder communication system, the wired fire department communication system shall be designed and installed in accordance with NFPA __
NFPA 72 ## Footnote NFPA 72 outlines the standards for fire alarm systems, including communication systems.
127
High Rise: Phone jacks shall be located at _______.
Every floor level in each enclosed exit stairway ## Footnote This ensures accessibility for emergency communication throughout the building.
128
A minimum of _______ handheld phone sets with cords 6 feet in length shall be maintained at the building control station.
6 ## Footnote One handheld phone set shall be permanently installed for consistent communication.
129
Fire alarm control units shall be _______ on paper and shall be utilized in accordance with their listing.
listed ## Footnote This ensures that the fire alarm control units meet safety and performance standards.
130
Every building and structure used or intended for sleeping purposes shall be provided with an automatic smoke-detection system. Exception: Buildings and structures in existence and in operation prior to January 1, _______.
1985 ## Footnote This exception applies to older buildings that may not have been retrofitted with modern smoke detection systems.
131
Manual Pulls are required in R-2 Occupancies that are _______ or more stories in heights.
16 ## Footnote R-2 Occupancies refer to residential buildings with multiple units.
132
Smoke detectors shall be located a minimum of _______ feet from cooking appliances. Exception is _______ feet or greater if having an alarm silence switch.
20, 10 ## Footnote This distance helps prevent false alarms caused by cooking activities.
133
New Construction: Fire Manual Pulls shall be located within _______ feet from exits or stairwells.
5 ## Footnote This proximity ensures that manual pulls are easily accessible in emergencies.
134
Activation of two or more detectors or sprinkler shall automatically cause illumination of means of egress of _______ foot candle, Activate any directional exit marking and a prerecorded message.
1 ## Footnote This illumination aids in safe evacuation during an emergency.
135
For Studios and Stages, heat detectors shall be spaced every _______ feet.
30 ## Footnote Proper spacing is crucial for effective heat detection in large areas.
136
Fire Department Communication outlets shall be located on every floor. _______ retained at the building Control Station.
6 ## Footnote This ensures that communication is maintained throughout the building.
137
Manual fire alarm boxes shall be _______ in color.
Red ## Footnote The red color is universally recognized for fire alarms.
138
139
Manual pulls are required _______ from exits or stairwells.
5 feet ## Footnote They are to be installed with a height of not less than 42 inches and not more than 48 inches from the ground.
140
Fire Alarms are required on all Assemblages when they exceed _______.
1,000 ## Footnote This is a critical threshold for fire alarm requirements.
141
Occupant Notification System shall have an Average Sound of _______ dBA above average ambient sound level or 5 dBA above maximum sound level.
15 ## Footnote This ensures that the notification system is audible in various conditions.
142
Fire Alarm Zones shall not exceed _______ square feet.
22,500 ## Footnote This limit helps in effective fire alarm management.
143
Emergency voice/alarm communication systems required by this code shall be designed and installed in accordance with NFPA __
72 ## Footnote NFPA 72 outlines the national standards for fire alarm systems.
144
Annunciation. Alarm, supervisory and trouble signals shall be annunciated in the main control unit by means of an audible signal and a visual display in accordance with NFPA __
72 ## Footnote This ensures proper notification and response to alarms.
145
Smoke & Heat Removal Vent opening exposed to _______ degrees for five minutes, must be fully open.
500 ## Footnote This temperature requirement is critical for effective smoke and heat removal.
146
Smoke Control Systems: Fan require a minimum of _______.
2 ## Footnote This specifies the minimum number of fan belts required.
147
Smoke & Heat removal Fans shall be rated at _______ F.
221 ## Footnote This rating is important for ensuring the fans can handle high temperatures.
148
Smoke Removal Systems shall be tested every _______ year(s)?
1 ## Footnote Regular testing is essential for maintaining system effectiveness.
149
All portions of active or engineered smoke control systems shall be capable of continued operation after detection of the fire event for a period of not less than either _______ minutes or 1.5 times the calculated egress time, whichever is greater.
20 ## Footnote This ensures that systems remain operational during critical evacuation times.
150
Ducts shall be constructed and supported in accordance with the California Mechanical Code. Ducts shall be leak tested to _._ times the maximum design pressure in accordance with nationally accepted practices.
1.5 ## Footnote This testing ensures the integrity of the duct system.
151
Measured leakage shall not exceed _______ percent of design flow.
100 ## Footnote This limit is crucial for maintaining system efficiency.
152
Early response Fast-Acting Sprinklers: Smoke removal Vents must open within _______ degrees above sprinkler activation.
100 ## Footnote This requirement helps in timely smoke removal.
153
Explosion Control: Walls and ceilings are designed to withstand an internal pressure of _______ Pound per Square Feet?
100 ## Footnote This specification is critical for structural integrity during explosions.
154
Atriums: No sprinklers required if ceiling is more than _______ feet above the floor.
55 ## Footnote This height exemption is based on fire safety regulations.
155
The minimum internal design for **Explosion Control** walls, ceilings, and roofs shall not be less than _______ times the max internal relief pressure.
5 ## Footnote This is a safety measure to ensure structural integrity during an explosion.
156
The **Clear Space** around FDC Connections shall be _______ inches wide & deep and _______ inches in height.
36, 78 ## Footnote This space is necessary for accessibility and safety during fire department operations.
157
Fire Department Connection signs must have letters that are a minimum of _______ inches.
6 ## Footnote Signs must state: 'Automatic Sprinkler' or 'Standpipe' or 'Test Connection'.
158
The **Fire Department Connection** sign when exiting a building shall be _______ inches high with 2" lettering stating FDC.
6 ## Footnote This ensures visibility and clarity for emergency responders.
159
Fire Department Connection treads shall be compatible with _______.
LAFD Hose threads ## Footnote This compatibility is crucial for effective firefighting operations.
160
The Fire Department Connection shall be tested _______ per Title 19.
Periodically ## Footnote Regular testing ensures functionality and compliance with safety standards.
161
Flammable and Combustible signs shall be how many inches high?
3 ## Footnote Proper signage is essential for safety in hazardous areas.
162
High Rise Pumps Fuel Supply shall be a minimum of _______ hours in full demand at 100% rated capacity.
2 ## Footnote This requirement ensures adequate fuel supply during emergencies.
163
Buildings more than _______ feet tall require a minimum of two sprinkler risers.
420 ## Footnote This is part of the Fire Protection - Special Use Occupancy regulations.
164
Occupancies having an occupied floor more than _______ feet above the lowest level for LAFI Apparatus shall be supplied by two mains.
120 ## Footnote This ensures sufficient water supply for firefighting in high-rise buildings.
165
Aircraft Hangers require a _______ hour wall rating.
2 ## Footnote This rating is necessary for fire resistance in aircraft hangers.
166
Carbon Monoxide Detection Requirements are found in _______.
NFPA 720 ## Footnote This standard outlines the installation requirements for carbon monoxide detectors.
167
Carbon Monoxide Detection must be installed throughout all new buildings; interconnection is not required in existing buildings built prior to _______.
January 1, 2011 ## Footnote This date marks the cutoff for existing building regulations.
168
Group R can have battery powered carbon monoxide alarms if built before _______.
January 1, 2011 ## Footnote This allows for flexibility in older residential buildings.
169
In Group E Occupancies, carbon monoxide alarm signals shall not be required to be automatically transmitted to an on-site location staffed by school personnel with an occupant load of _______ or less.
30 ## Footnote This regulation helps manage alarm systems in smaller educational settings.
170
The authority to require implementation of a **Fire Watch** lies with the _______.
Chief ## Footnote This ensures that a qualified individual oversees fire safety measures.
171
The owner, manager, or person in charge shall assign as many personnel required by the _______.
Chief ## Footnote This ensures adequate staffing for fire watch duties.
172
The minimum internal design for **Explosion Control** walls, ceilings, and roofs shall not be less than _______ times the max internal relief pressure.
5 ## Footnote This is a safety measure to ensure structural integrity during an explosion.
173
The **Clear Space** around FDC Connections shall be _______ inches wide & deep and _______ inches in height.
36, 78 ## Footnote This space is necessary for accessibility and safety during fire department operations.
174
Fire Department Connection signs must have letters that are a minimum of _______ inches.
6 ## Footnote Signs must state: 'Automatic Sprinkler' or 'Standpipe' or 'Test Connection'.
175
The **Fire Department Connection** sign when exiting a building shall be _______ inches high with 2" lettering stating FDC.
6 ## Footnote This ensures visibility and clarity for emergency responders.
176
Fire Department Connection treads shall be compatible with _______.
LAFD Hose threads ## Footnote This compatibility is crucial for effective firefighting operations.
177
The Fire Department Connection shall be tested _______ per Title 19.
Periodically ## Footnote Regular testing ensures functionality and compliance with safety standards.
178
Flammable and Combustible signs shall be how many inches high?
3 ## Footnote Proper signage is essential for safety in hazardous areas.
179
High Rise Pumps Fuel Supply shall be a minimum of _______ hours in full demand at 100% rated capacity.
2 ## Footnote This requirement ensures adequate fuel supply during emergencies.
180
Buildings more than _______ feet tall require a minimum of two sprinkler risers.
420 ## Footnote This is part of the Fire Protection - Special Use Occupancy regulations.
181
Occupancies having an occupied floor more than _______ feet above the lowest level for LAFI Apparatus shall be supplied by two mains.
120 ## Footnote This ensures sufficient water supply for firefighting in high-rise buildings.
182
Aircraft Hangers require a _______ hour wall rating.
2 ## Footnote This rating is necessary for fire resistance in aircraft hangers.
183
Carbon Monoxide Detection Requirements are found in _______.
NFPA 720 ## Footnote This standard outlines the installation requirements for carbon monoxide detectors.
184
Carbon Monoxide Detection must be installed throughout all new buildings; interconnection is not required in existing buildings built prior to _______.
January 1, 2011 ## Footnote This date marks the cutoff for existing building regulations.
185
Group R can have battery powered carbon monoxide alarms if built before _______.
January 1, 2011 ## Footnote This allows for flexibility in older residential buildings.
186
In Group E Occupancies, carbon monoxide alarm signals shall not be required to be automatically transmitted to an on-site location staffed by school personnel with an occupant load of _______ or less.
30 ## Footnote This regulation helps manage alarm systems in smaller educational settings.
187
The authority to require implementation of a **Fire Watch** lies with the _______.
Chief ## Footnote This ensures that a qualified individual oversees fire safety measures.
188
The owner, manager, or person in charge shall assign as many personnel required by the _______.
Chief ## Footnote This ensures adequate staffing for fire watch duties.