When lowering Generator MW for turbine shutdown what is the minimum load that should be maintained?
Why?
50 MW
prevent motoring of turbine generator
When in OP L-8 (separating from the grid while maintaining Rx power > 30%) whose permission is required to operate below 15%?
Operations Manager