How deep are power poles to be buried?
10% of total length +2’
Absolute minimum depth is 5 feet
What are the four transmission voltages we use?
A. 46kV
B. 138kV
C. 345kV
D. 500kV
What are the two distribution voltages we use?
A. 4kV
B. 13.8kV
What is the maximum ampacity for Distribution class voltages?
200A
What is the maximum ampacity of Feeder class voltages?
600A
What are the four wire sizes commonly used for Distribution class wire?
2 ACSR is the most common size used
A. #6 hard drawn copper
B. #4 hard drawn copper
C. #2 ACSR**
D. 1/0 ACSR
What are the two wire sizes commonly used for overhead Feeder class wire?
A. 477 ACSR**
B. 4/0 ACSR
477 ACSR is the most commonly used for Feeder class wire
What size wire is used when going from a pad mounted transformer to a pedestal?
350 kcmils
What size wire is used when going from a pedestal to a 200A service?
4/0
When is a CT can (current transformer) required in order to place a meter base?
401A+
What are the two documents needed for easements?
A. Legal description
B. Sketch or “exhibit” drawing
A type 9 PME/PMH has how many fuses?
6 fuses
A type 10 PME/PMH has how many fuses?
No fuses
A type 11 PME/PMH has how many fuses?
3 fuses
What two wire sizes are commonly used for the static wire?
A. 3-#6 copper weld**
B. #2 ACSR
3-#6 copper weld is most commonly used