A valve with two disks and two seats. One disk opens, with the pressure & one against. With the forces balanced, it opens easily.
The PRV automatically reduces high pressure and maintains a lower delivery pressure.
They are used for heating systems, cookers, city water makeup, control air, gas or oil to a boiler.
A valve that only allows flow in one direction.
Safety valve, water level control valve, drain valve, fill valve, non-return valve, plug valves, check valves, gate valves, globe valves and a maxon valve.
It is pressure testing the boiler for leaks.
Close, lock and tag all valves and blank or remove all safeties. Fill the boiler completely with room temperature water to 1-1/2 times the working pressure and call for the inspector.
This should be done on new boilers, after turbine cleaning the boiler tubes and any time repairs are made on the pressure vessel.
Make sure you know the source and correct if possible. New boiler and those which have accumulated a deposit of oil and grease must be cleaned by boiling out with an alkaline detergent solution. This is a combination of tri-sodium phosphate and di-sodium phosphate. Superheaters must be given a steam blow to loosen debris from the inside surfaces and feed-water systems need flushed. Follow boiler designer recommendations and consult your chemical treatment company.
A bag is a bulge in a boiler tube, caused by an overheated area under the scale. Small bags can be heated and driven back into place.
Blisters are the separation of layers in the boiler steel caused by a combination of imperfections in the boiler plate and overheating. Blisters must be cut away and replaced.
Scale is mineral solids in boiler water being deposited on the heating surfaces. It is caused by high TDS (totally dissolved solids) and improper treatment of boiler water.
The eating away of metal as a result of low alkaline water, the presence of free oxygen or both, in the water.
The weakening of boiler steel as the result of inner crystalline cracks caused by long exposure to a combination of stress and high alkaline water
Zeolite water softener, distiller or chemicals.
Nitrate, phosphates, sulfite, conductivity, hardness, pH and chloride.
Polymers, Phosphates amines and chelates.
Priming is boiler water being carried out of the boiler with the steam. It can be reduced by lowering the fire rate, reducing the foaming or lower the water level in the boiler.
It is the condensate carried along with the steam flow through the pipe striking an elbow or tee, possibly rupturing the pipe.
Turn off the fire or close the steam valve.
It is an unequal distribution of flame contacting the tubes or furnace walls and can be prevented by correct operation and maintenance of the equipment.
When cleaning fire tubes, a knocker raps the inside of a tube, cracking the scale off the outside. When cleaning water tubes, a cutter head rotates inside, cutting and crushing the scale. Always keep the cutter head moving!
A hydrostatic test should be done after the cleaning.
Sometimes acid cleaning by a qualified person is necessary after mechanical cleaning.
Pits are small hollow spots that could develop into holes. They are caused by oxidation.