Switched cap banks may be switched automatically based on?
Vars Voltage Amps Time and date Temperature up
After opening a cat bank how long must you wait before closing it? Why?
A minimum of five minutes
Because that’s how long it takes for the resistor inside the cap bank to bleed off the left over capacitance voltage that’s left over in the cap after de-energizing
Pre rigged switches can only be rigged to open or close?
Open
What must the neutral have at an AR if there is phase to neutral load beyond the AR?
The neutral must have a CT on it at the AR
Can you ground the neutral beyond an AR? Why?
No, escaping current
Why do we install AR’s?
Sectionalizing-bad acting circuits
Protection- far from the sub, can’t create enough phase to ground fault current
Change mode of operation- bulletin 322
I’m a bulletin 322 area during red flag warning what must be done before re-energizing?
The circuit must be patrolled
Why do we have ground banks?
Gives a delta circuit ground protection and also to stabilize an ungrounded neutral
3 mechanisms PE gear need to function?
Transfer mechanism ( the arm that moves )
Control mechanism ( control box )
PT ( preferred side has a 3 phase bank to sense voltage )