What is the timing after a fault for a mid point RCS?
DOM SW-11 page 7
Can you use a load break elbow to energize a capacitor?
No. Do not use LBE’s to energize or de energize a capacitor bank.
DOH CC-5
At what temperature difference between cable and load break elbow can the load break elbow not be used?
Load break elbow can not be used if there is a 10 degree difference between cable and load break elbow.
Elbow must also be scheduled to be changed out.
DOM CC-5
What’s the formula to find full load amps on a capacitor bank?
What’s the rule of thumb? For 12kv.
KVAR times 1000 divided by voltage times 1.73
Rule of thumb take a 0 off the KVAR number and divide remaining number by 2
Example for 12kv KVAR 600 Remove a 0 60 Divide by 2 30 full load amps
If you are not behind CLF, above how many amps of fault duty are you not allowed to close energized load break elbows?
5,700 amps of fault duty
DOM CC-5 page 11
Can you de-energizes a transformer with bayonet fuses?
If so, can it have any load on it?
Yes. As long as each bayonet fuse does not exceed100 amps.
DOM TR-2 attachment 3
What’s the maximum amps you can break with a break safe tool?
300 amps
What are the 5 switches that can break capacitive voltage?
How many amps of circulating current can a KPF Switch break? 12kv 16kv? 33kv?
12 & 16kv
12’ arm no whiskers: 150amps
No whiskers: 100amps
Whiskers: 350amps
33kv
12’ arm no whiskers: 0 amps
No whiskers: 0 amps
Whiskers: 80 amps
Portal overhead switches.
Where is ferroresonance not a consideration?
DOM TR-8 pg 8
What are the 4 R’s when switching on 4kv?
Make Recloser solid
Take Reads
Block Regulators and turn off controls
Make ground Relay solid
What would happen if you didn’t block the ground relay and closed the bypass switch on a RAR? I’m
If current goes through a RAR and doesn’t return on the RAR then the RAR will open on ground. So when then bypass switch is closed not all the current will flow back through the RAR, some will flow throw them bypass switch.
After replacing the fuses inside a load brake fuse cabinet what is the sequence for energizing the cabinet?
After replacing fuses, the fuse cabinet shall be energized with the line side load break elbow first then the load side load break elbow will be used to pick up the load.
**DOM PD -4 4.1.h
What precautions must be taken prior to energizing any new piece of cable or equipment?
What describes a RAJ switch?
1st position solid to the bus
2nd position and 4th position can be open, closed, or tie
3rd position is solidly connected to the tie position.
** 3rd step book underground switches pg 14
What are the four reasons we bypass an RAR?
What is the rule of thumb to figure out full load amps on a cap bank for 4kv 12kv and 16kv
4 kv-Kvar divided by 7
12 kv- kvar divides by 20
16 kv - kvar divides by 30
How many amps can a load break elbow break?
200 amps
DOM CC-5