ASS Flashcards

(22 cards)

1
Q

Which of the are ASS loads or functions?

A

steam jet air ejectors
hot water heating system
TDMFW gland sealing steam

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

Which statement describes the function and operation of the aux building aux steam header isolation valve?

A

the valve isolates aux steam to the aux building automatically during steam line break conditions (determined by aux building ambient temperature)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What is a problem when aux boilers supply the aux steam system?

A

the chemicals used to treat the aux boiler feed water can cause conductivity alarms on the aux condensate flash tank outlet, causing effluent water to dump to the liquid waste system

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

The plant is at 10% power during S/U following cold shutdown. What is the source of steam for the steam jet air ejectors?

A

aux boiler master controller, with steam from an operating auxiliary boiler

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

What is the MP3 EPA permit limit for max aux boiler fuel oil usage?

A

8 gal per minuter per boiler

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

IF the aux boiler fuel oil consumption rate were to increase significantly above its normal rate, what concerns arise?

A

EPA permit does not allow more than 8 gpm per boiler

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

Plant tripped from 100% power in mid-summer. How many aux boilers will be started and why?

A

1 boiler, since plant heating loads are minimal

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

Which of the following is the sequence for an emergency shutdown of a auxiliary boiler?

A

press “manual trip”, then “purge and reset”

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

During startup and warmup of aux boiler, when does the atomizing medium automatically switch from service air to steam?

A

when steam drum pressure reaches 100 psig

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

What will cause the aux building steam header isolation valves to auto close?

A

aux building temp exceeds 127 F

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

??

A

a pulsating flame which expands and contracts

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

How long is the burner gun manually purged after fuel is shut off?

A

2 mins

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

What would be the consequence of opening the “B” aux boiler fuel oil tank outlet, and closing the “A” aux boiler fuel oil tank outlet?

A

“B” tank will slowly transfer to the “A” tank because the recirc valves were not swapped

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

What is the source of aux steam for U2?

A

U3 aux steam header supplies a reducing station in CPF

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

When is the #2 atomizer allowed to be placed in service?

A

during a changeout of a dirty #1 atomizer while the boiler is already operating

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

How is the main flame ignited in the aux boilers?

A

a propane igniter flame is used to light the main oil flame

17
Q

What are the lift set points for the “A” aux boiler code safety valves SV26A and SV25A?

A

170 and 175 respectively

18
Q

It is mid-august, 70F.

Can the entire U3 aux steam header system be shut down?

A

no, aux steam needed to supply loads like condenser air ejectors steam supply

19
Q

How is U2 aux steam system removed from service while keeping U3 ASS in system?

A

U2 ASS reducing values are isolated using both inlet and outlet manual isolations

20
Q

The U2 ASS is S/D and isolated from U3 for the summer. Can the U2 aux condensate system be shutdown?

A

yes, shutting down the U2 ASS supply V991 results in all inputs to U2 aux condensate being isolated as well

21
Q

When warming a cold (ambient) aux boiler, what is the fuel oil flow rate set and why?

A

1.2 gpm to reduce heat rate within manufacturer recommendation

22
Q

When S/D an aux boiler, how is the fuel oil system shut down so that the burner gun will remain filled with oil?

A

the boiler is shutdown by pressing the “oil gun stop” PB