SDS Flashcards

(9 cards)

1
Q

The steam dump system is designed to accommodate a load rejection without a reactor trip to a max of __ % rated thermal power.

A

40

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

Which is the most severe load rejection the plant can withstand without either a Rx trip or atmospheric steam dump lifting?

A

50% step load rejection

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

The reactor trips from 100% power.

The “A” reactor trip breaker fails to open.

What will be the final RCS Tavg?

A

557 F

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

The lo-lo Tave block signal can be bypass for ____ steam dump valves to allow performing a controlled plant cooldown.

A

bank 1

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

Which of the following must exist to “arm” steam dumps?

A

condenser vacuum must be available

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

The steam pressure mode of the turbine bypass valve control system is used to control RCS temp by:

A

modulating steam dumps in response to steam header pressure error

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

The bank 1 “cooldown” steam dump valves consist of ___ and are arranged to direct steam into _____.

A

3MSS-PV47A/B/C; condensers 1A, 1B, 1C

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

Steam dumps in Steam Pressure Mode
Pressure controller in auto
All circ pumps running

What condition will directly close the condenser steam dumps valves and then PREVENT from auto opening?

A

main steam header pressure as sensed by PT-507 fails low

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

Plant tripped from 100% power.

What condition would prevent the condenser dumps from being able to control RCS temp?

A

MSIV closed

How well did you know this?
1
Not at all
2
3
4
5
Perfectly