Plant tripped. SI/CIA actuated due to steamline break outside containment.

What describes how the reactor plant chilled water system is affected?

A

RPCCW supplies cooling to a few CDS loads inside containment. The operating CDS chillers stop

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What is the purpose of maintaining a minimum flow through chilled water recirculation control valve?

A

ensure a minimum flow through the chillers during low load conditions

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What is the programmed time delay between successive CDS compressor starts?

A

30 mins

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What system acts as the heat sink for the reactor plant chilled water system?

A

RPCCW

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

What is not a function of the CDS system?

A

cooling for the reactor plant sample panel sample coolers

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

One of the normal loads on the reactor plant chilled water system is:

A

CAR cooling coils

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

One of the purposes of the CDS system is to suply chilled water to:

A

RWST coolers

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

What is the function of the pre-rotation vanes?

A

to compensate for variations in load

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

What is the function of the 25 PSID oil pressure switch when the CDS chiller start pushbutton is pushed?

A

prevents the start of the chiller if not satisfies after 30 seconds

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

What is the power supply for 3CDS-CHL1C?

A

4160 V bus 34A

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

Increasing recirculation flow through chiller recirc flow control valve indicates which of the following?

A

decreasing load on CDS system

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

Why must the CDS chiller lube oil heater be energized for 12 hours, or the compressor oil changed, prior to starting the unit?

A

prevents lube oil foaming upon compressor start

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

Describe why the CDS surge tank is pressurized with nitrogen to 7-11 psig

A

provide NPSH to pumps and provide corrosion control

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

Given the following:

PEO finds the “C” CDS chiller tripped
Switchgear 86E relay not tripped
Chiller “cycling/flow interlock” alarm at the local panel is present

What signals causes the chiller to trip?

A

RPCCW condenser water flow low

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

The limit on CDS chilled water circulating pump is:

A

two starts in one hour if the motor comes to rest between starts

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

Makeup water for the CDS system comes from:

17
Q

During CDS chiller startups and shutdowns, when will the lube oil pump automatically start and stop?

A

starts when the chiller control switch is taken to “START” and stops 45 seconds after the chiller stops