What are the two methods that can be used to compute fire flow test results?

A

Graphical analysis and mathematical method

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What is the easiest way to determine how much water is flowing from a hydrant outlet?

A

Refer to prepared tables for nozzle/outlet discharge

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

Which of the following is the BEST way to locate partially closed valves before they pose a problem?

A

Routine testing

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

Which type of hydrant should be located as close as possible to the location requiring flow test results?

A

Test hydrant

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

Valves in water systems are usually the _____ type and located underground.

A

nonindicating

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Which material(s) will be needed to complete the inspection of fire hydrants?

A

Pitot tube and gauge

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

What is the purpose of a fire flow test?

A

To determine the rate of fire flow available for fire suppression

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

What information do calculations or graphical analyses from fire flow tests provide?

A

Amount of water flow from individual hydrants

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

How often should control valves be exercised?

A

At least once a year

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

The basic water supply system component that includes water pumps is:

A

means of moving water.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

What should inspectors refer to when trying to determine the coefficient of discharge for a specific nozzle?

A

Manufacturer’s recommendations

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

How often should hydrant inspections take place?

A

At least once a year

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

Fire protection engineers have established _____ as the minimum required residual pressure when computing the available water for area flow-test results.

A

20 psi (140 kPa)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

In general, where should the test hydrant be located in relation to the flow hydrant when testing a single hydrant?

A

Between the flow hydrant and the water supply source

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

Unless some effort is made to steady the _____, the movement of the water will make an accurate reading difficult.

A

pitot tube

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

During hydrant inspections, inspectors need to verify that the clearance between the bottom of the discharge outlet and the grade is at least:

A

15 inches (380 mm).

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
17
Q

What is used to indicate a hydrant’s ownership and flow capacity?

A

Paint

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
18
Q

Water distribution and storage systems include:

A

storage tanks, control valves, piping systems, and hydrants.

19
Q

Which type of control valve usually has a rubber or rubber-composition seat that is bonded to the valve body?

A

Butterfly valve

20
Q

A _____ delivers water from the source to the distribution system without pumping equipment.

A

gravity system

21
Q

Who is responsible for the inspection, testing, and maintenance of private water supply systems?

A

Facility owners/occupants

22
Q

A _____ may be an open lake or pond or an enclosed structure.

23
Q

Water mains that convey large quantities of water to various points are:

A

primary feeders.

24
Q

Before beginning a flow test, an inspector should verify that the air chamber on the pitot tube is:

25
If the needle on the pressure gauge is fluctuating, read and record the valve located:
in the center between the high and low extremes.
26
Small water mains that serve individual fire hydrants are:
distributors.
27
Which basic water supply system component includes lakes, reservoirs, and ponds?
Water sources
28
The interlocking network of water mains that compose a water distribution system is referred to as a:
grid system.
29
Storage tanks located throughout a water distribution system are usually constructed of:
concrete or steel.
30
What entity is usually responsible for public water supply systems?
Local government
31
What size outlets should generally be used to conduct hydrant flow tests?
2½-inch (65 mm)
32
Which type of hydrant is designed for use in climates that have freezing temperatures?
Dry-barrel
33
When testing multiple hydrants, where should the test hydrant be located?
Centrally located
34
Before conducting a fire flow test, an inspector should notify:
a water department official.
35
The system for moving water by installing pumps in the distribution system when elevation pressure cannot provide sufficient pressure is a:
direct pumping system.
36
Which type of obstructions include growths, crusts, or rust on the inside walls of water mains?
Encrustations
37
The BEST method for evaluating the capabilities of a water supply system is:
reviewing documentation.
38
Which tanks are used to stabilize or balance the pressures on distribution systems at times of peak demand?
Gravity tanks
39
Why do workers close control valves?
To initiate repairs
40
Hydrant discharge outlets are considered standard if they contain:
one large (4- or 4½-inch [100mm or 115 mm]) outlet and two hose outlet nozzles for 2½-inch (65 mm) couplings.
41
Which problem is the MOST important when it comes to elevated tanks?
Limitation of pressure available from the tanks
42
Which water main includes intermediate pipes that interconnect with primary feeders to create a grid?
Secondary feeders
43
Which tanks are located at ground level and provide a water supply source for fire pumps?
Suction tanks