Automatic alarm-initiating devices are more commonly known as:
detectors.
When more than two strobes are in the field of vision, the strobes used for notification of fire must be synchronized to flash:
at the same time.
A(An) _____ is a warning of a fire emergency or dangerous condition that demands immediate attention.
alarm signal
A measurement for audible occupant notification of fire is required to be made at:
5 feet (1.5 m) above the floor.
Which component’s acceptance testing includes testing pull stations, detectors, bells, and strobe lights?
Alarm-initiating and occupant notification appliances and circuits
The total sound pressure produced by audible occupant notification of fire appliances must not exceed:
120 dBA.
Which type of manual pull station may be confusing to certain occupant/operators?
Double-action
The most common types of alarm-signaling systems used for signaling a fire alarm in a structure are:
audible notification appliances.
Which type of fixed-temperature heat detector uses two types of metal with different heat-expansion ratios?
Bimetallic
Plans for the complete fire detection and alarm system should be submitted for review and approval by the:
local authorities.
In addition to horns, bells, and strobes, notification may also include:
voice evacuation systems.
The level of loudness is a measurement of sound pressure measured in:
decibels.
Which type of smoke detector works on all types of fires and usually responds more quickly to smoldering fires than ionization smoke detection?
Photoelectric smoke detectors
Multistory facilities should have at least _____ pull station(s) on each floor.
1
What needs to be done any time there is a change to fire detection and alarm-signaling software?
The system should be COMPLETELY tested.
The fire alarm component that serves as the brain of an alarm system is called the:
fire alarm control unit (FACU).
Where are rotating beacons used for occupant evacuation notification?
Large industrial and commercial complexes
Which rate-of-rise heat detector is designed for use in areas subject to regular, but slow, temperature changes?
Rate-compensation heat detector
What should an inspector do when conditions that may trigger an unwanted alarm or environmental conditions that may negatively affect a system are recognized?
Recommend corrective action
Which activity is MOST likely to be witnessed by an inspector during acceptance testing?
Inspection of conduits for solid connections and proper support
What document is sometimes required in order to prevent an inspector from checking a system that may not be installed correctly?
A record of completion from the system installer/manufacturer
All components of emergency voice/alarm systems should be tested at least:
annually.
The preferred type of automatic alarm device in residences and health and institutional care facilities is a:
smoke detector.
Which supervising station does not provide inspection, testing, or maintenance services?
Remote