IRPI power supply for rod bottom B/S, bypass B/S, and racks and modules
PP-61 circuit 1
(480V Bus 5 feeds MCC-15 which feeds PP-61)
IRPI RTGB LED’s power supply
IB-7A circuit 10
IF you loos IB-7A what happens?
RTGB IRPI LED’s extinguish, but Rod Bottom bistable lights will still illuminate if rod drops
If you loose PP-61 what happens?
LED indicators on RTGB will default to “0” steps/inches, GREEN indications.
Rod bottom mistable light will not illuminate
LCO 3.1.4 Rod Group ALignment LImits
Rod Alignment Requirments for ITS
(For bank demand positions >=200 steps)
Each rod shall be within 15inches of its bank demand position
LCO 3.1.4 Rod Group Alignment limits
Rod Alightment requirements
(For bank demand postions <200 steps)
Each rod shall be within 7.5 inches of the average of the individual rod positions in the bank
A dropped Rod is still operable
A stuck rod is not operable
LCO 3.1.4 Rod Group Alignment LImits
For condition A
(One or more rods inoperable)
3.1.4 Rod Group Alignment limits
For condition B
(One rod not within alignmnet limits)
How many steps on RTGB for step counters
0-250 steps
Each step is how many inches
5/8”
Rod Bottom Bypass Bistables allows you to do what?
Allows you to operate below 35 steps without giving Rod Bottom alarm (20 steps)
IRPI
Red Rod Bottom LIght indicator illuminates when a rod is what?
les than 12.5inches, or 20 steps from the bottom of the core
IRPI