Rod Control System Flashcards

(35 cards)

1
Q

Auto Rod Control system is designed to

A

Keep Tavg consistent with Tref.
Uses Tavg and compares to First stage turbine pressure

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

When in AUTO is there any OUTER motion?

A

NO OUTER MOTION IN AUTO

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

Rod Control

Auto Rod Contorl system is designed to do what?

A

REstore program Tavg folowing a scheduled or transient step shange in load of 10% or ramp change of 5% per minute within the range of 15-100% power

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

1 step is how much movement?

A

5/8 inch

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

ITS Maximum time for rod drop?

A

1.8 seconds

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

CRDM Out Sequence

A
  1. Hold on stationary gripper
  2. Latch on movable gripper
  3. Unlatch on stationary gripper
  4. Pull up the lift armature, raising the drive rod 5/8”
  5. Latch the stationary gripper
  6. Unlatch the movable gripper
  7. Drop the lift armature
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

CRDM in sequence

A
  1. Hold on stationary gripper
  2. Pull up the lift armature
  3. Latch the movable gripper
  4. Unlatch the stationary gripper
  5. Drop the lift armature, lowering the drive rod 5/8”
  6. Latch the stationary gripper
  7. Unlatch the movable gripper
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

How long does it take for a single step to be performed?

A

780 milliseconds (.78 seconds)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

Rod Drive Motor Generator
Powered from, output?

A

480V Bus 2B/3
Outputs 260V at 58.3 hertz

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

If a bank is individually selected to move, what does this do?

A

No bank overlay. Must be returned to the position held before individual banks were moved.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

Reading Power Cabinets
1AC is?

A

Group 1 in Shutdown Bank A
Group 1 in Control Bank A
Group 1 in Control Bank C

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

Reading Power Cabinets
2BD is?

A

Group 2 Shutdown Bank B
Group 2 Control Bank B
Group 2 Control Bank D

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

Power Cabinet Urgent Alarm does what?

A
  1. Energizes red light on affected Power Cabinet
  2. Stops all rod motion in affected Power Cabinet
  3. Loss Overlap in unaffected cabinets
  4. RTGB alarm
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

Power Cabinet Urgent alarm caused by?

MR. LLP

A
  • Multiplexing Error
  • Regulation Failure
  • Logic Error
  • Loose or missing Card
  • Phase Failure
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

Can you still move rods on a Urgent Power Cabinet alarm?

A

Not on effected cabinet but if you select an infidivual bank you can move that bank but you loose designed overlap

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

If you misposition a rod bank out of overlap what must be done before returning to MANUAL OR AUTO on the selector switch

A

Whatever bank was moved must be moved back to correct postion per procedure

17
Q

Power Cabinet Non-Urgent alarm does what?

A

Loss of Power supply causes an urgent alarm if INWARD rod motion is demanded. (causes a logic error)
If OUTWARD rod motion is demanded will ratchet or drop

We place rods in manual and do not attempt any motion until repairs comp

18
Q

A Logic Cabinet Urgent alarm does what?

A
  • Inhibits all rod motion
  • Energizes red light at logic cabinet
  • RTGB alarm
19
Q

A Logic Cabinet Urgent alarm is caused by?

SLO

A
  • Secondary Cycler
  • Loose or missing card
  • Osciallator
20
Q

Power Cabinet and Logic Cabinet non urgent alarms are caused by?

A

Power supply failure

21
Q

Overlap works how?

A
  1. Control Bank A out 128
  2. Control Bank A/B out 100
  3. A stops at 228 steps total
  4. B goes 28 steps (now its at 128 steps)
  5. B/C go out 100
  6. B Stops when its at 228 steps out
  7. C goes 28 more steps (128 steps)
  8. C/D goe 100 steps
  9. C Stops at 228 steps
  10. D goes 118 more steps (Stays at 218 steps out)

Total of 602 steps

22
Q

Rod Control Logic compares what?

A

Median Tavg to Tref

23
Q

How much difference does Tavg have to be above Tref before Rod movement? when does movement stop?

A

1.5 degrees F. starts Rod insertion, once Tavg and Tref are within 1 degree of each other Rod movement stops

24
Q

Rod Insertion Limits setpoint comes from?

A

Linear function of Median Delta T

25
Rod Insertion Limits do what?
* Ensure adequate SDM * LImit the worth of ejected rod * Ensure Proper Axial Flux
26
Start up Push Button does what?
Resets: Primary Cycler counter Secondary Cycler counter P-A converter Internal memory and alarm circuits Group step counters on RTGB Bank overlap counter
27
S/D Banks A & B move how fast? | Individual banks selected only
68 steps a minute
28
Control Banks move how fast? | Individual banks selected or in manual
45 steps a minute
29
When in auto how fast do Rods move?
* 8-72 steps a minute * 8 steps from 1.5-3 degrees difference * ramps up to 72 steps from 3-5 degree difference which at top speed is 45inch/min
30
DC hold cabinet supplies what? and holds how many rods?
125/70 VDC 125 for latching 70 fo holding 5 Rods can be held at one time
31
Define SDM
The instantaneous amount of reactivity by which the Rx is subcritical or would be subcritical from its present condition assuming all full-length rod cluster assemblies (shutdown and control) are fully inserted except for the single rod cluster assembly of highest reactivity worth that is assumed to be fully withdrawn.
32
# Rod Control RCCAs in each group?
A,B,C all have 8 D has 5 Shutdown banks A/B have 16
33
# Rod Control Fans that cool the CRDM?
HVH-5A/B, which are cooled by CCW. Remember backwards cooling.
34
# Rod Control What defines a fully inserted rod?
20 steps or 12 inches withdrown, the same as the Rod Bottom Light Setpoint
35