Sequencer
What turns on after 5 seconds?
A/B/C SI pump starts
(B only if racked in)
SI only
Sequencer
What turns on after 15 seconds?
A/B RHR pumps start
SI only
Sequencer
What turns on after 20 seconds?
A/C SW pumps start
(Signal to start both SWBPs. SI auto start, SBO waits until 30psig in SW header)
Both SI and SBO
Sequencer
What tuns on after 25 seconds?
B/D SW pumps start
(Signal to start both SWBPs. SI auto start, SBO waits until 30psig in SW header)
Both SI and SBO
Sequencer
What turns on after 30 seconds?
1/3 HVH units start on SI
CCW pump B/C start on SBO
Sequencer
What turns on after 35 seconds?
2/4 HVH units start
SI only
Sequencer
39.5 seconds?
A/B AFW starts
Both SI and SBO
List the SI sequencer
5 sec- A/B/C SI pumps
15 sec- A/B RHR pumps
20 sec- A/C SW pumps (SWBPs)
25 sec- B/D SW pumps (SWBPs)
30 sec- 1/3 HVH units
35 sec- 2/4 HVH units
39.5 sec- A/B AFW pumps
List the SBO sequencer
20 sec- A/C SW pumps (SWBPs with 30psig)
25 sec- B/D SW pumps (SWBPs with 30psig)
30 sec- B/C CCW pumps
39.5 sec- A/B AFW pumps
What happens if a safety injection singal comes in while a blackout sequence is in progress?
Which sequencer sheds loads?
Blackout
What loads are not shed on a blackout?
MCC-5/16 - MCC-6/18
What turns off a CCW pump? Dealing with the sequencer.
Having 3 signals, UV, SI, and Spray
What turns off charging pump? Dealing with the sequencer.
UV and SI
SI Sequencer must have what to start?
Power on respective bus. If an SI sequence starts after a black out, remember that 10 seconds have to pass before the Bus has power.
Blackout sequencer starts
When power on the bus is gone. 10 seconds for the edg to sync.
When will A CCW pump start if it was not already running?
Low pressure if power is available on DS bus. 90 seconds required for the DS bus to receive power from the DSDG if its lost.
If the EDG output breaker is closed what does it stop from happening?
CCW pump start on low pressure for affected Bus.