Why does AUX XFMR 1-2 have one coil powering 4 kV bus E and the other coil powering 4 kV bus D, F, G and H?
E has two condensate booster pump sets and the HDP , which combined total more load than all loads the other buses can carry.
What conditions must be met to open 4 kV non- vital S/U feeder bkr?
Close 4 kV S/U feeder bkr?
Open- take to open
Close- synch switch on
- take to close
What conditions must be met to open 4 kV non-vital AUX feeder bkr?
Close 4 kV AUX feeder bkr?
Open- switch to open
Close- synch switch to on
- MOD full open or close
- 25 kV ISO ground switch open
- switch to closeDescribe how the “manual” automatic xfr to S/U and xfr to AUX work?
=> simultaneously closes one bkr and opens other
What is danger of not matching flags?
Which flags have greater consequences of not matching?
If bkr trips on overcurrent, you will get no alarm
Aux bkr - If bkr trips on O.C. The lockout feature will not prevent an UNDESIRABLE xfr to S/U
What 4 kV busses are power from what DG?
Bus F - DG 3
Bus G - DG 2
Bus H - DG 1
What switches are used to manually xfr to S/U (12 and 4 kv)
What actions do you do if during xfr both bkrs remain closed
All xfr’s to and from S/U shall be done with manual xfr switches (using individual switches causes large circulating currents and damage)
Immediately Trip one of bkrs
What differential overcurrent protection exists on 4 kV busses D and E if powered from S/U?
What is difference if buss powered from AUX?
AUX
- xfr to S/U is locked out
What is main difference in differential overcurrent protection on the vital 4 kV busses versus the non-vital?
On vital buses, more automatic xfrs are locked out……for example if initially powered from:
Aux……..xfr to S/U and xfr to DG locked out
S/U…….xfr to DG locked out
Bkr trips for vital 4 kV busses?
Aux
S/U
DG
Aux - O.C. - diff O.C. - 86 G1 - 86 G11 S/u - O.C. - diff O.C. DG - DG diff - bus diff - DG s/d relay - o.c. * - rev pwr * - DG loss of field*