Sequence of opening steam supplies to MFP?
LP gov valves open first (hot reheat), not enough steam pressure to operate pump => HP gov valves open (MSS). When (hot reheat) LP has enough steam pressure, the HP will close down. At 100% power, HP closed, MFP operating off LP only
What is FCV-420
Interlocks
Mainfeedwater long recirc valve
Discharge #1 fw htrs -> MN condenser
Used for chemistry cleanup of fw
If any FW htr outlet > 320 deg valve will shut (won’t open) to protect MN cond from water hammer
What gives FWI signal?
SI P-14 (Ls/g > 90% NR) - turbine Trip - MFP Trip - FWIV's - FRV and Byp
P-4 w/ Tave < 554
- FRV and Byp
How do you reset FWI signal (3)
Reset SI
Cycle RTB
Reset FWI
Precautions and limitations for MFW (3)
How are MFP protected from overheating during low flow conditions?
FCV-53 and 54 open to provide minimum recirc to condenser of 1000 gpm
Pump running for recirc valve to open (>60 d/p)
Steam sources to #1FWHtrs (3)
-HP turbine 3rd stage extraction
-MSR HP drain tank
-MSR excess steam vent
What happens to FWH #1 on a hi hi level (2)
-Trip closed MSR HP drain tank drips
-vent air supply to non-return valves from 3rd stage HP ext steam
What actions happen if Hi level in #2HDT(1)
Trips closed the drips valve from the #1FWHTR
What are the MFW Reg Valves and purpose(3)
FCV-510/520/530/540
-control S/G level via the DFWCS>30% power
-isolates on a FWI
-manual operation: reverse acting valve
What are the MFW Reg bypass valves and purpose?(3)
-FCV-1510/1520/1530/1540
-controls S/G level via the DFWCS<30% power
-isolates on a FWI
-no manual operation
What are the MFW isolation valves and purposes?
FCV-438/439/440/441
-isolates on a FWI