Purpose of ASW?
Basic flowpath?
Alignment?
Automatic starts for ASW pumps?
What starts require switch in auto?
Automatic trips of ASW pumps
O.C. Load shed (4kv UV)
What is only common failure that could take out both ASW pumps?
How is this prevented?
Common floor drain header => flooding in one pump room can go through drains and flood other room
How is ASW pump motor able to breath since its in a watertight room?
What is purpose of ASW-601, where is it controlled from?
Crosstie between units, allows one unit to supply other ASW
U-1 MCR (480v 1F)
What are the air bottles in the CCW hx room there for?
The inlets to the CCW hx (ASW side) are air close, fail open valves.
If instrument air lost (100#) the bottles provide backup air to maintain valves closed so the in service CCW hx isn’t robbed cooling flow (8 hrs)
Precautions and limitations for ASW